7. Output Configuration for Electric Valve Control
Each of the 8 outputs can be configured to drive an electric valve (solenoid valve) typically used in
heating and cooling systems for floor panels.
Use this output configuration when you want to drive an ON/OFF type solenoid valve,
without motor reductor. In this type of valve one of two states (open or closed) is
associated with the condition of valve powered, the other to valve not powered.
If you use this configuration, the control algorithm must be resident in the control device
(thermostat, etc. ..).; the relay act only to power or not the valve.
The functional diagram of each output configured as electric valve control is represented in the
following scheme:
2 POINT CONTROL OBJECT :
receive 1 bit commands to open and close the valve.
CONTINUOUS CONTROL OBJECT: receives 1 byte commands (0% -100%) to open and close
the valve throught a PWM sequence.
LOCK FUNCTION OBJECT:
if enabled, according to the receipt of a 1 bit telegram,
realizes a function for enabling / disabling the opening and
closing of the valve
1 BIT STATUS OBJECT:
send information about the position (open / closed) of the
valve using a 1 bit telegram
1 BYTE STATUS OBJECT:
send information about the proportion of active regulation
using a 1 byte telegram
RELAY
LOCK FUNCTION
OBJECT
2 POINT CONTROL
OBJECT
CONTINUOUS CONTROL
OBJECT
1 BIT STATUS
OBJECT
1 BYTE STATUS OBJECT