BO08A01KNXFI01010002.DOC
Din Rail 8 Output Module– Product Handbook
42/51
Eelectron SpA, Via Magenta 77/22, I-20017 Rho (MI), Italia
+39 02.9316681 +39 02.93507688
[email protected] www.eelectron.com
BO08A01KNXFI01010002.DOC
C.F. e P.IVA 11666760159
Capitale sociale: 800.000,00€ interamente versato
Tribunale di Milano 359157-8760-07
CCIAA Milano 148549
8.3. Louvres
automatic
movement
If the channel is configured for Venetian control (Parameter “
Shutter Type
= Venetian”) it is
possible to enable an automatic movement of the louvres which is executed at the end of
movements of the shutter.; these movements are:
Movement for scene command (if brings the shutter in a position different from totally up)
Movement at the end of a lock or alarm state (if brings the shutter in a position different
from totally up)
Movement for a Position % command (if brings the shutter in a position different from
totally up )
This automatic function moves the louvres up after a shutter down movement and down after a
shutter up movement.
KNX PARAMETER
SETTINGS
Louvres automatic movement
Never
After up movements
Always
After down movements
Set when the automatic movement must start.
Number of automatic steps after move up
1 ÷ 15
Number of automatic steps after move down
1 ÷ 15
This parameter set the time of the movement : if this parameter is set to “2” and
“Step time for
louvres movement (x 100ms)”
is set to “3” then the automatic movement
is 300ms x 2 = 600ms
Pause time between 2 step move ( x100ms)
3 ÷ 10
Set the minimum time delay between 2 step movements.
8.4. Additional
Functions
In BO08A01KNX for channels configured for shutters 3 additional functions can be enabled:
SCENE FUNCTION
: The scene function manage two possible commands to the device:
perform scene
, that is a command to create a specific condition;
learn
scene
, that is a
command to memorize the current status (at the moment the command is received) of the
shutter position, and then reproduce it once the perform command is received.
LOCK FUNCTION
: this function according to the command received from the bus, blocks
the shutter in a specific condition when a “lock on” command arrives, this state is kept until
a “lock off” command is received; any command received during the period in which the
block is activated is not executed.
ALARM FUNCTION
: this function allows linking the shutter channel to a rain or wind
sensor to protect it from damage.
[!]
This function (if enabled) requires the sensor linked to
send cyclically a telegram, even if The alarm is off. If the shutter does not receive any
telegram for a defined time (see parameter “
supervision time for alarm
”) it goes in the
alarm position as if it would have been received a alarm telegram.