![Eelectron BO08A01KNX Скачать руководство пользователя страница 28](http://html.mh-extra.com/html/eelectron/bo08a01knx/bo08a01knx_product-handbook_2366505028.webp)
BO08A01KNXFI01010002.DOC
Din Rail 8 Output Module– Product Handbook
28/51
Eelectron SpA, Via Magenta 77/22, I-20017 Rho (MI), Italia
+39 02.9316681 +39 02.93507688
[email protected] www.eelectron.com
BO08A01KNXFI01010002.DOC
C.F. e P.IVA 11666760159
Capitale sociale: 800.000,00€ interamente versato
Tribunale di Milano 359157-8760-07
CCIAA Milano 148549
Example of logic function:
If a relay has AND function enabled and delay on activation/deactivation enabled.
RELAY CONTROL
LOGICAL FUNCTION
RESULT BEHAVIOUR
0 0
0
-
1
0
0
Start a delay on deactivation
1
1
1
Start a delay on activation
6.11. Lock Function
When lock function is enabled it allows, as a result of receiving a telegram on the
<Output x> Lock
Function;
to switch the relay in a defined state and force it to maintain this state even if the object
switching value changes.
KNX PARAMETER
SETTINGS
Initial Value for Lock Object
Value “0”
Value “1”
This parameter selects the value of the lock object after a power on; appropriately changing this
value it is possible to start the output channel related to the lock function as “locked” or
“unlocked”. (
See note 1
).
Telegram for Lock Activation
Telegram “0”
Telegram “1”
This parameter selects the values associated to the “lock” or “unlock” condition.
Relay Position when Lock is Active
Relay is Deactivated
Relay is Activated
This parameter selects the state the relay must assume when the “lock function” becomes active”.
(
See note 2
).