6.6. Function ON/OFF with delay
In this configuration it is possible to set a time delay on the relay activation (T
ON
) and also a delay
time for the relay deactivation (T
OFF
)
The opening and closing of the contact, when the parameters are different from zero, occurs later
than the receipt of the telegram, activation and deactivation delays are set separately
KNX PARAMETER
SETTINGS
Delay on Activation
True
False
Delay on Deactivation
True
False
Delay on Activation (Base Time)
1 sec.
1 minute
1 hour
Delay on Activation (Factor)
1…255
The delay time between the receipt of a telegram and the execution of the command is given by :
Delay of Activation Time = Delay on Activation (Base Time) x Delay on Activation (Factor)
Delay on Deactivation (Base Time)
1 sec.
1 minute
1 hour
Delay on Deactivation (Factor)
1…255
The delay time between the receipt of a telegram and the execution of the command is given by :
Delay of Deactivation Time = Delay on Deactivation (Base Time) x Delay on Deactivation (Factor)