background image

BO08A01KNXFI01010002.DOC 

 

 

 

Din Rail 8 Output Module– Product Handbook 

 

10/51 

Eelectron SpA, Via Magenta 77/22, I-20017 Rho (MI), Italia 
+39 02.9316681  +39 02.93507688  
[email protected]  www.eelectron.com 

BO08A01KNXFI01010002.DOC 

C.F. e P.IVA 11666760159 
Capitale sociale: 800.000,00€ interamente versato 
Tribunale di Milano 359157-8760-07 
CCIAA Milano 148549 

 

5.  Output Configuration Fan Coil Actuator 

 

This mode should be chosen first in the ETS configuration of the device as if it is enabled, commits 
the outputs from 1 to 5 exclusively. 
Outputs 1 and 2 are interlocked and are dedicated to the operation of switching from cooling mode 
(air conditioning / cooling) to heating mode and vice versa. 
Outputs from 3 to 5 are interlocked and dedicated to the management of the 3 speed of the Fan 
Coil. 
 
Communication objects 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

OUT 3 ÷5 

 

HEATING

 

SPEED 1 

FEEDBACK

 

SPEED 2 

FEEDBACK

 

SPEED 3 

FEEDBACK

 

 

OUT 1 ÷2 

SPEED 1

 

SPEED 2

 

 

SPEED 3

 

SPEED CONTINUOUS 

CONTROL (%)

 

HEATING / COOLING  

FEEDBACK

 

SPEED CONTINUOS 

CONTROL FEEDBACK

 

 

HEATING / COOLING 

 

COOLING 

Содержание BO08A01KNX

Страница 1: ...07688 info eelectron com www eelectron com BO08A01KNXFI01010002 DOC C F e P IVA 11666760159 Capitale sociale 800 000 00 interamente versato Tribunale di Milano 359157 8760 07 CCIAA Milano 148549 Din Rail 8 Output Module BO08A01KNX Product Handbook Product Description Din Rail 8 Output Module Order Code BO08A01KNX Document Version 1 1 Date 23 01 2014 ...

Страница 2: ...ntrol 12 6 Output Configuration for Generic Load Control 14 6 2 General Parameters 15 6 3 Relay Functions 16 6 4 Additional Functions 17 6 5 Function ON OFF 18 6 6 Function ON OFF with delay 19 6 7 Function ON with delay timing OFF 20 6 8 Function Continuous Switching 25 6 9 Communication objects 26 6 10 Logic Function 27 6 11 Lock Function 28 6 12 Scene Function 29 7 Output Configuration for Elec...

Страница 3: ...e versato Tribunale di Milano 359157 8760 07 CCIAA Milano 148549 Any information inside this manual can be changed without advice This handbook can be download freely from the website www eelectron com Exclusion of liability Despite checking that the contents of this document match the hardware and software deviations cannot be completely excluded We therefore cannot accept any liability for this ...

Страница 4: ...d in pairs for the management of roller shutters and blinds up to 4 channels Channels A to D Outputs can be configured in pairs for management of Motor Reductor or for solenoid valves with 3 point control or for ventilating grilles up to 4 channels Channels A to D Fan Coil Actuator for 2 4 pipes systems for Heating Cooling with 3 speed motors relays from 1 to 5 Different configurations can exist s...

Страница 5: ...o a maximum of 50 group addresses The maximum number of logical associations allowed for the device is 63 this means that the maximum number of logical connections between communication objects and group addresses is 63 Caution there is a limit to the number of associations that can be created on the same device between transmission communications objects i e inputs and receiving communication obj...

Страница 6: ...unction selected later for each KNX PARAMETER SETTINGS Delay on Power up 3 15 sec 2 15 seconds Through this parameter is possible to set the delay of transmission of telegrams after a power on by selecting the time by which the device is allowed to send telegrams In large systems after a power failure or shutdown this delay avoids to generate excessive traffic on the bus causing slow performance o...

Страница 7: ... ON LINE sending time 10 min 1 hr 12 Hr 24 Hr Through this parameter it s possible to enable a cyclical sending on the bus of a 1 bit telegram with value 1 this sending has a programmable time interval This message can be used to detect errors like power failure or breakage of the device to a monitoring system or to a bus control system KNX PARAMETER SETTINGS All Valve Closed Disabled Enabled All ...

Страница 8: ...utputs 6 7 and 8 remain available as output for generic loads or electric valves control outputs 7 and 8 can be still configured for control of shutters blinds or motor reduction driver Output 1 2 Configuration Output are independent Output are coupled Here it is possible to set if outputs are independent and therefore can be set with functions which use only one relay at a time generic loads and ...

Страница 9: ...oupled Shutter Driver Motor Reduction Output 1 and 2 works in coupled mode this parameter selects the function shutter management or motor reduction management Identical parameter for output coupled 2 3 4 5 7 8 Output 2 Configuration Same values of Output 1 Configuration Output 3 Configuration Same values of Output 1 Configuration Output 4 Configuration Same values of Output 1 Configuration Output...

Страница 10: ...ld be chosen first in the ETS configuration of the device as if it is enabled commits the outputs from 1 to 5 exclusively Outputs 1 and 2 are interlocked and are dedicated to the operation of switching from cooling mode air conditioning cooling to heating mode and vice versa Outputs from 3 to 5 are interlocked and dedicated to the management of the 3 speed of the Fan Coil Communication objects OUT...

Страница 11: ...il speed 2 ON OFF contact OUT 5 FAN COIL SPEED 3 Connect to fan coil speed 3 ON OFF contact For 2 pipes systems Uscita Descrizione Collegamento OUT 1 VALVE HEAT COOL Connect to heating cooling valve ON OFF contact OUT 2 See note 1 OUT 3 FAN COIL SPEED 1 Connect to fan coil speed 1 ON OFF contact OUT 4 FAN COIL SPEED 2 Connect to fan coil speed 2 ON OFF contact OUT 5 FAN COIL SPEED 3 Connect to fan...

Страница 12: ...rol of 3 speed fan coil can be achieved with 3 communication objects 1 bit which accept commands on off or with a 1 byte communication object for a proportional control KNX PARAMETER SETTINGS Delay between Speed Changes Sec 1 255 This parameter set the pause time between the switching off the relay which control one speed and the switching on of another relay to activate the next speed Object type...

Страница 13: ...eramente versato Tribunale di Milano 359157 8760 07 CCIAA Milano 148549 KNX PARAMETER SETTINGS Limit Value Speed 2 3 90 80 70 60 Limit value of control to pass from Speed 2 to Speed 3 Limit Value Speed 1 2 10 20 30 40 Limit value of control to pass from Speed 1 to Speed 2 Lower Limit Value 0 5 10 Limit value of control to pass from Speed 1 to OFF For example if values 70 30 and 0 are selected 100 ...

Страница 14: ...RAMETER SETTINGS Sending state telegram Disable When status changes On request The parameter defines the behavior of the object as Disabled Not available When status changes updated on switching and transmitted on the bus On request updated on switching spontaneously and not transmitted on the bus but only on request 6 Output Configuration for Generic Load Control The functional diagram of each ou...

Страница 15: ...r down ON OFF STOP no movement When bus voltage fall down under approximately 18V device enters the power down routine and it is possible to set the status of the relay status See note 1 Behaviour on power up ON OFF Keep status on power down On power up it is possible to set the status of each relay with this parameter see note 2 NOTES 1 the device has to accumulate the energy it needs to switch t...

Страница 16: ...it is possible to set a delay between the reception of a telegram and the switch of the relay for both telegrams activation and deactivation ON with delay timing OFF it is possible to set a delay between the reception of a telegram of activation and the switch of the relay the OFF switch is automatic after a configurable time staircase timer Continuous switching with this function the relay when a...

Страница 17: ...e is associated to the ON or OFF status 6 4 Additional Functions In BO08A01KNX 3 additional function can be enabled LOCK FUNCTION this function according to the command received from the bus blocks the relay in a specific condition when a lock on command arrives this state is kept until a lock off command is received any command received during the period in which the block is activated is not exe...

Страница 18: ...bunale di Milano 359157 8760 07 CCIAA Milano 148549 6 5 Function ON OFF The relay switches when a message is received on the Relay Command Object Behavior of the relay set to NO and NC when activation telegram is telegram 1 0 1 1 0 Telegram NO is closed Contact type NO NO is open NO is closed Contact type NC NO is open Behavior of the relay set to NO and NC when activation telegram is telegram 0 1...

Страница 19: ...the parameters are different from zero occurs later than the receipt of the telegram activation and deactivation delays are set separately KNX PARAMETER SETTINGS Delay on Activation True False Delay on Deactivation True False Delay on Activation Base Time 1 sec 1 minute 1 hour Delay on Activation Factor 1 255 The delay time between the receipt of a telegram and the execution of the command is give...

Страница 20: ...tive for a time TLS that can be set by a parameter when TLS expires it turns off automatically It is also possible to set a delay on activation time TON see ON with delay function KNX PARAMETER SETTINGS Delay on Activation True False Delay on Activation Base Time 1 sec 1 minute 1 hour Delay on Activation Factor 1 255 The delay time between the receipt of a telegram and the execution of the command...

Страница 21: ... com BO08A01KNXFI01010002 DOC C F e P IVA 11666760159 Capitale sociale 800 000 00 interamente versato Tribunale di Milano 359157 8760 07 CCIAA Milano 148549 Duration of relay activation TLS and ON delay time TON are programmable by ETS 1 Telegram NO is closed Contact type NO NO is open TON TLS ON delay time TON can be disable by ETS 1 Telegram NO is closed Contact type NO NO is open TLS ...

Страница 22: ...and switch off the relay without waiting the end of the timing phase False On receiving a OFF command the device ignores the command and continues the timing phase the load is deactivated at the end of the set time and it is not possible to deactivate it using a bus command Warning Function True False Warning Time seconds before time ends 15 sec 30 sec 1 minute 2 minutes Switch Off Time 1 0 sec 1 ...

Страница 23: ...er Mode Extension Mode This allows you to set the behaviour of the device when it receives a ON command while the staircase timing is running Ignore On receiving a ON command the device ignores it and goes on executing the timing Trigger Mode On receiving a ON command the device restart the stairs light time execuiting the whole time again Extension Mode On receiving the command the device extends...

Страница 24: ...ron com BO08A01KNXFI01010002 DOC C F e P IVA 11666760159 Capitale sociale 800 000 00 interamente versato Tribunale di Milano 359157 8760 07 CCIAA Milano 148549 Duration of relay timing is re trigge able 1 1 Telegram NO close Normally Open NO open Timing Timing NO close Normally Close NO open Timing Timing Extension Mode 1 1 1 Telegram NO close Normally Open NO open TLS TLS TLS 3 x TLS ...

Страница 25: ... Switching In this configuration it is possible to activate the relay to perform a continuous ON OFF switching that can be started or ended by a specified activation telegram TON and TOFF can be set by parameters KNX PARAMETER SETTINGS Time ON Base Time 1 sec 1 minute 1 hour Time ON Factor 1 255 The duration time of the ON state for the relay is ON Duration Time Time ON Base Time x Time ON Factor ...

Страница 26: ...48549 Activation Telegram Telegram 1 Contact Type Normally Open 1 0 Telegram NO close Normally Open NO open TON TOFF TON TOFF TON KNX PARAMETER SETTINGS Start Continuous Switching on Power Up False True If set to True this parameter enable the activation of continuous switching on power up without waiting for the activation telegram it starts automatically If this parameter is set to TRUE the cont...

Страница 27: ...o use every time a telegram is received on the logical object or on the control object the logical operation is calculated again and the result is taken as a command for the relay KNX PARAMETER SETTINGS Logic function AND OR XOR This parameter selects the logical operation Initial Value for logic Operation Value 0 Value 1 This parameter selects the value the logical object must have on power up se...

Страница 28: ...lock function is enabled it allows as a result of receiving a telegram on the Output x Lock Function to switch the relay in a defined state and force it to maintain this state even if the object switching value changes KNX PARAMETER SETTINGS Initial Value for Lock Object Value 0 Value 1 This parameter selects the value of the lock object after a power on appropriately changing this value it is pos...

Страница 29: ... active Keep previous state and don t ignore telegrams the output channel returns to its condition prior to the activation of the block unless you have received a telegram on the switch object or scenario in this case the last command received is executed NOTES 1 If the parameter Initial Value for Lock Object has the same value of Telegram for Lock Activation happens that on power up the output ch...

Страница 30: ...d numbers are from 0 to 63 64 means scene is not active Initial value Scene X Contact Open Contact Close For the 4 possible scene this number allow to initialize the status associated to previously selected scene number avoiding to execute the store scene procedure If the store scene is done this value is overwritten Learn Scene Enabled Disabled This parameter enable disable the output channel fro...

Страница 31: ...other to valve not powered If you use this configuration the control algorithm must be resident in the control device thermostat etc the relay act only to power or not the valve The functional diagram of each output configured as electric valve control is represented in the following scheme 2 POINT CONTROL OBJECT receive 1 bit commands to open and close the valve CONTINUOUS CONTROL OBJECT receives...

Страница 32: ...316681 39 02 93507688 info eelectron com www eelectron com BO08A01KNXFI01010002 DOC C F e P IVA 11666760159 Capitale sociale 800 000 00 interamente versato Tribunale di Milano 359157 8760 07 CCIAA Milano 148549 7 2 Main Parameters ETS parameters when control value telegram is 1 bit ETS parameters when control value telegram is 1 byte ...

Страница 33: ...must set this parameter at the value Valve Closed and the parameter see below Activation telegram with value Telegram 0 close the valve Activation telegram Telegram 0 close the valve Telegram 1 close the valve It is possible to set a parameter to determine if the function is activated with a telegram 0 and then off with 1 or is activated with telegram 1 and then off with 0 Cycle Base Time For PWM ...

Страница 34: ...king Valve Activation Period 1 day 3 days 10 days Determines the maximum period of inactivity allowed Lock Function Disabled Enabled When lock function is enabled it allows switching the relay in a defined state and forcing it to maintain this state even if the it receives 1 bit or 1 byte control commands Behaviour on power down Valve Open Valve Close STOP no movement When bus voltage fall down un...

Страница 35: ...ice has to accumulate the energy it needs to switch the relays during the power on phase and stores it into capacitors For this reason when a power down is detected the device has the energy to switch all the 8 relays only if it has been powered from at least 60 seconds and it has not done a full 8 relay switch from at least 20 seconds It is strongly recommended not to select a full 8 relay switch...

Страница 36: ... the same described in par 6 11 Lock Function This function can be enabled or with 1 bit commands than with 1 byte commands KNX PARAMETER SETTINGS Initial Value for Lock Object Value 0 Value 1 This parameter selects the value of the lock object after a power on appropriately changing this value it is possible to start the output channel related to the lock function as locked or unlocked See note 1...

Страница 37: ...tion prior to the activation of the block unless you have received a telegram on the switch object or scenario in this case the last command received is executed NOTES 1 If the parameter Initial Value for Lock Object has the same value of Telegram for Lock Activation happens that on power up the output channel starts in lock mode waiting for a unlock telegram in order to become active Note that ev...

Страница 38: ...n for shutter and blinds Outputs can be configured in pairs for the management of roller shutters and blinds up to 4 channels Channels A to D Channel Output Function Output Function CH A OUT 1 closed move up OUT 2 closed move down CH B OUT 3 closed move up OUT 4 closed move down CH C OUT 5 closed move up OUT 6 closed move down CH D OUT 7 closed move up OUT 8 closed move down COUPLED RELAYS SCENE O...

Страница 39: ... PARAMETER SETTINGS Shutter Type Shutter Venetian Select Venetian if the shutter has louvres select shutter if it is a roller shutter Shutter travel time sec 0 3000 This parameter set the total travel time for shutter Extra Time for shutter travel sec 1 255 This parameter indicates the number of seconds to add to the travel time for all the movements that bring the shutter completely up or down St...

Страница 40: ...and can be sent to the device using a percentage value the value is relative to the percentage of closure 10 50 etc 0 shutter totally up shutter totally down VALUE SHUTTER POSITION through 1 byte telegram the information on the current shutter position can be sent the value is relative to the percentage of closing KNX PARAMETER SETTINGS Delay on move up Disabled Enabled Enable disable a delay betw...

Страница 41: ...ente versato Tribunale di Milano 359157 8760 07 CCIAA Milano 148549 These parameters can be used if you want to drive double doors In this case one door must start first in opening and the other must start first in closing KNX PARAMETER SETTINGS Step time for louvres movement x 100ms 1 180 This parameter selects how long the movement for every step of the louvres is visible only if shutter type is...

Страница 42: ... move down 1 15 This parameter set the time of the movement if this parameter is set to 2 and Step time for louvres movement x 100ms is set to 3 then the automatic movement is 300ms x 2 600ms Pause time between 2 step move x100ms 3 10 Set the minimum time delay between 2 step movements 8 4 Additional Functions In BO08A01KNX for channels configured for shutters 3 additional functions can be enabled...

Страница 43: ...ry channel it is possible to store a maximum of 4 output scene KNX PARAMETER SETTINGS Scene Number X 0 64 For the 4 possible scenes this number is the unique identifier for the scene valid numbers are from 0 to 63 64 means scene is not active Initial value Scene X Values between 0 and 100 in steps of 5 For the 4 possible scene this number allow to initialize the position associated to previously s...

Страница 44: ...propriately changing this value it is possible to have the shutter channel related to the lock function as locked or unlocked See note 1 Lock Activation Telegram Telegram 0 Telegram 1 This parameter selects the values associated to the lock or unlock condition Shutter Position when Lock is Active Move Up Move Down Stop no movement This parameter selects the state the relay must assume when the loc...

Страница 45: ...X PARAMETER SETTINGS Supervision Time for Alarm min 1 120 min This parameter selects how long the supervision time for the alarm function is If this time is set for example to 30 min the shutter need to receive at least one time in 30 min a telegram from the sensor even if the telegrams means no alarm It this not happens the alarm became active lack of supervision and need to receive a no alarm te...

Страница 46: ...osition after lock and alarm This parameter set the final position of the shutter after the end of a lock or an alarm condition of course if both functions are no active the value of this parameter is not considered KNX PARAMETER SETTINGS Shutter position after lock and alarm Move Up Move Down Previous position and ignore telegrams This parameter selects the values associated to the alarm conditio...

Страница 47: ...me Communication object scheme 2 POINT CONTROL OBJECT 1 bit command to open close the valve completely CONTINUOUS CONTROL OBJECT 1 byte command 0 100 to set the valve position LOCK FUNCTION OBJECT if enabled according to the receipt of a 1 bit telegram realizes a function for enabling disabling the opening and closing of the valve 1 BIT STATUS OBJECT send information about the position open closed...

Страница 48: ...316681 39 02 93507688 info eelectron com www eelectron com BO08A01KNXFI01010002 DOC C F e P IVA 11666760159 Capitale sociale 800 000 00 interamente versato Tribunale di Milano 359157 8760 07 CCIAA Milano 148549 9 2 Main Parameters ETS parameters when control value telegram is 1 bit ETS parameters when control value telegram is 1 byte ...

Страница 49: ...tween 2 movements 1 bit telegram Activation telegram Telegram 0 Telegram 1 It is possible to set a parameter to determine if the Open movement is activated with a telegram 0 and then Close with 1 or vice versa Sending State Telegram Disabled When status changes On request Disabled Status is never transmitted ad related communication object is not visible When status changes Status is transmitted e...

Страница 50: ...intain this state even if the it receives 1 bit or 1 byte control commands Behaviour on power up Valve Open Valve Close STOP no movement On power up it is possible to set the status of each valve with this parameter 9 3 Lock Function When lock function is enabled it allows as a result of receiving a telegram on the Output x Lock Function to switch the relay in a defined state and force it to maint...

Страница 51: ...ts with lock function already active it does not go automatically in the position defined by the parameter Relay Position when Lock is Active because this behaviuor is determined only by the parameter Behaviour on power up 9 4 Function VALVES ALL CLOSED When at least one output is configured on the device type Electric Valve Driver or Motor Reduction Driver Solenoid Actuator you can enable a commu...

Отзывы: