System Functions
77
1
Set The Number Of Days Until The First Test Report
If you require the first test to report (Contact ID Event Code 602) the day after you are
installing the control panel and you have programmed the repeat interval between each test
report for every 7 days, you will need to set when the first test report will occur. If the first test
report is not set using this Installer Code Function, the first test report will be sent to the base
station receiver in the number of days programmed in the repeat interval. Refer to
"LOCATION 360 - 366" on page 187 for setting the test report time and repeat interval.
How To Set The First Test Report
1.
Enter your
followed by
1
and the
button.
Three beeps will be heard and the
STAY
and
AWAY
indicators will begin to flash.
2.
Enter the
to wait (1 - 15 days) until the first test report is required.
3.
Press the
button when finished.
Two beeps will be heard and the
STAY
and
AWAY
indicators will extinguish. The
system will now return to the disarmed state.
+
1
+
+
+
Each time you enter Installer's Programming Mode after you have set when the first test
report will occur, the first test report time will default back to the repeat interval time
between each test report as set in “LOCATION 366”.
Test reports will not report if the Subscriber ID Number is 0000. The number of days
decrements by one at 2400 hours as set in "LOCATION 901 – 904" on page 210.
Example
If you programmed the repeat interval in the test reports for every seven days, but wish to have
the first test report to begin in two days time, follow the sequence outlined below;
1234
+
1
+
+
2
+
Electronics Design and Manufacturing Pty Limited
ISSUE130
Содержание Solution 862
Страница 1: ...Solution 862 Installation Manual ISSUE 1 30...
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 15: ...Introduction This section includes the following Introduction Features Quick Start Zone Defaults Zone Types...
Страница 43: ...Codepad Indicators This section includes the following CP5 Eight Zone LED Codepad CP5 Eight Zone LCD Codepad...
Страница 74: ...74 Solution 862 Installation Manual ISSUE130 Electronics Design and Manufacturing Pty Limited...
Страница 111: ...Remote System Operations Via Telephone This section includes the following Remote Arming Via The Telephone...
Страница 118: ...118 Solution 862 Installation Manual ISSUE130 Electronics Design and Manufacturing Pty Limited...
Страница 149: ...User Codes This section includes the following Installer Code User Codes User Code Priority...
Страница 154: ...154 Solution 862 Installation Manual ISSUE130 Electronics Design and Manufacturing Pty Limited...
Страница 188: ...188 Solution 862 Installation Manual ISSUE130 Electronics Design and Manufacturing Pty Limited...
Страница 212: ...212 Solution 862 Installation Manual ISSUE130 Electronics Design and Manufacturing Pty Limited...
Страница 228: ...228 Solution 862 Installation Manual ISSUE130 Electronics Design and Manufacturing Pty Limited...
Страница 237: ...Appendices This section includes the following Telephone Anti Jamming Test Reports Only When Armed...
Страница 240: ...240 Solution 862 Installation Manual ISSUE130 Electronics Design and Manufacturing Pty Limited...
Страница 245: ...Programming Sheets...
Страница 254: ...254 Solution 862 Installation Manual ISSUE130 Electronics Design and Manufacturing Pty Limited...
Страница 255: ...Index...
Страница 262: ......