The refrigerant expansion valves must be adjusted at startup.
Firmly attach a thermocouple or other temperature sensor to the suction
tubes.
Insulate the sensor and all around the suction tube with 1/2” thick
insulation for at least three inches on either side of the temperature sensor.
Tape the insulation to prevent air flow from changing the temperature
reading.
Locate and identify the refrigerant sight glasses.
Locate and identify the expansion valves associated with each sight glass.
Startup Prepare to Adjust Expansion Valves
Air-Cooled Direct Expansion, Water-Cooled Direct Expansion, Glycol-Cooled
Direct Expansion, Air-Cooled DualCool, Glycol-Cooled DualCool,
& FreeCool Units Only
ST
ARTUP
EXAMPLE
Appearance, location, and
quantity of component
s
may vary
.
Содержание EN Series
Страница 1: ......
Страница 103: ...OEM User manual ...
Страница 104: ......
Страница 106: ......
Страница 108: ......
Страница 110: ......
Страница 115: ...OEM CAREL code 030221791 rel 2 1 21 09 07 7 KUE 4 L H A1 A2 S2 S1 V3 V1 P S V X X1 Y Y1 KUE CC ...
Страница 123: ...OEM CAREL code 030221791 rel 2 1 21 09 07 15 4 2 Single phase wiring diagram INTERNAL TAM CP2 ...
Страница 124: ...OEM CAREL code 030221791 rel 2 1 21 09 07 16 4 3 Single phase wiring diagram INTERNAL TAM with contactor CP4 ...
Страница 125: ...OEM CAREL code 030221791 rel 2 1 21 09 07 17 4 4 Single phase wiring diagram EXTERNAL TAM with contactor CP3 ...
Страница 126: ...OEM CAREL code 030221791 rel 2 1 21 09 07 18 4 5 Three phase wiring diagram EXTERNAL TAM with contactor CP3 ...
Страница 127: ...OEM CAREL code 030221791 rel 2 1 21 09 07 19 4 6 Three phase wiring diagram INTERNAL TAM with contactor CP4 ...
Страница 141: ......