Ecosaire
®
EN Series Precision Air Conditioner Owners Manual
Product Description Major Cooling Options
6
Ecosaire
®
July 2009
Data subject to change without notice.
DESCRIPTION
Air-Cooled Direct Expansion
The
Ecosaire
®
unit operates its refrigeration system as needed to
control room conditions.
Heat is transported via refrigerant-vapor flow to an outdoor air-cooled
condenser. The refrigerant liquifies in the condenser and returns to the
Ecosaire
®
unit.
Outdoor condensers
are rated for 95°F (35°C) ambient with optional
models available for higher or lower ambient temperatures. They are
constructed of copper tubes and aluminum fins. A factory-wired control
panel is provided for field connection. Fan cycling and pressure-
actuated fan speed control maintain head pressure of either compressor
down to -20°F (-29°C). Optional flood-back controls are available for
either 30°F (-34°C) or -40°F (-40°C) operation.
See
Installation - Piping
for details.
Water-Cooled Direct Expansion
The
Ecosaire
®
unit operates its refrigeration system as
needed to control room conditions.
Heat is transported via refrigerant-vapor flow to an
internal water-cooled condenser. The refrigerant liquifies
in the condenser and re-circulates.
Water is pumped through the condenser to carry the
heat away. Proper flows and and temperatures of water
or other fluid must be provided by others. See
Installation - Piping
.
The cooling water entering the unit must have minimum
temperature of 65°F (18°C). Contact the factory for lower
temperatures.
cooling water or
other fluid,
(by others)
Ecosaire
Ecosaire
Remote Condenser
service isolation
valves (by others)
EXAMPLE
Appearance, location, and
quantity of component
s may
vary
.
EXAMPLE
Appearance, location, and
quantity of component
s may
vary
.
Содержание EN Series
Страница 1: ......
Страница 103: ...OEM User manual ...
Страница 104: ......
Страница 106: ......
Страница 108: ......
Страница 110: ......
Страница 115: ...OEM CAREL code 030221791 rel 2 1 21 09 07 7 KUE 4 L H A1 A2 S2 S1 V3 V1 P S V X X1 Y Y1 KUE CC ...
Страница 123: ...OEM CAREL code 030221791 rel 2 1 21 09 07 15 4 2 Single phase wiring diagram INTERNAL TAM CP2 ...
Страница 124: ...OEM CAREL code 030221791 rel 2 1 21 09 07 16 4 3 Single phase wiring diagram INTERNAL TAM with contactor CP4 ...
Страница 125: ...OEM CAREL code 030221791 rel 2 1 21 09 07 17 4 4 Single phase wiring diagram EXTERNAL TAM with contactor CP3 ...
Страница 126: ...OEM CAREL code 030221791 rel 2 1 21 09 07 18 4 5 Three phase wiring diagram EXTERNAL TAM with contactor CP3 ...
Страница 127: ...OEM CAREL code 030221791 rel 2 1 21 09 07 19 4 6 Three phase wiring diagram INTERNAL TAM with contactor CP4 ...
Страница 141: ......