CAREL code +030221791 - rel. 2.1 – 21/09/07
6
2.
INSTALLATION: dimensions, weights, hose connections
2.1
Positioning
•
To favour steam distribution, position the appliance so as to minimise the length of the steam outlet pipe (max 4 m). The unit has
been designed for wall mounting; the wall must be able to support the weight of the unit during operation.
•
The cylinder of the humidifier may reach temperatures above 60°C.
•
Make sure that the humidifier is level.
KUE*R / KUE*1 / KUE*2 / KUE*3
Italian
English
Raccordo di alimentazione 3/4 “ Gas maschio
Supply connection 3/4“ Gas male
Raccordo di drenaggio diam. 32 mm
Drain connector dia. 32mm
N. 4 fori di fissaggio 6x10
4 fastening holes 6x10