OEM
CAREL code +030221791 - rel. 2.1 – 21/09/07
9
2.3
Drain
2.4
Supply
To simplify installation, it is recommended to use the CAREL hose with an inside diameter of 6 mm and an outside diameter of 8
mm (code 1312350APN) and the revolving ¾G connection, either straight (code 9995727ACA) or 90° (code 9995728ACA),
available upon request.
A shut-off tap and a mechanical filter should be installed to trap any solid impurities.
The drain water is connected using a section of rubber or plastic hose resistant to 100°C, with a recommended inside diameter of
32 mm or 40 mm for the 25 to 45kg/h models (compliant with DIN 19535, UNI 8451/8452).
The drain connector is suitable for heat sealing with polypropylene drain pipes.
IMPORTANT WARNING: the drain hose must be free, without backpressure and with a drain trap immediately
downstream of the connection to the humidifier.
2.5
Checks
The following conditions represent correct water connection:
•
installation of a shut-off tap in the supply water line;
•
presence of a mechanical filter in the supply water line;
•
water temperature and pressure within the allowed values;
•
drain hose resistant to temperatures of 100°C;
•
minimum inside diameter of the drain hose of 25 mm or 36 mm for the 25 to 45kg/h models;
•
minimum slope of the drain hose greater than or equal to 5°;
•
electrically
non-conductive
sleeve.
•
presence of a drain trap in the drain hose
IMPORTANT WARNING: when installation is completed, flush the supply hose for around 30 minutes by piping the water
directly into the drain without sending it into the humidifier. This will eliminate any scale or processing residues that may
block the fill valve or cause foam when boiling.
models
KUE*R* KUE*1* KUE*2*
KUE*3*
KUE*4*
Max. instant drain flow l/min
~ 4
~ 4
~ 4
~ 4
~ 22.5
Darin water attachment
(mm)
32 32 32 32 40
Min. ID of the drain hose
25 25 25 25 36
models
KUE*R*
KUE*1* KUE*2*
KUE*3*
KUE*4*
Max. instant supply flow
l/min
0.6
0.6
0.6 1.2 4
Supply water attachment
¾ ”G
Male
¾ ”G
Male
¾ ”G
Male
¾ ”G Male ¾ ”G Male
Min. ID of the sill pipe or
hose
6 6 6 6 6
Table 2.4.1
Содержание EN Series
Страница 1: ......
Страница 103: ...OEM User manual ...
Страница 104: ......
Страница 106: ......
Страница 108: ......
Страница 110: ......
Страница 115: ...OEM CAREL code 030221791 rel 2 1 21 09 07 7 KUE 4 L H A1 A2 S2 S1 V3 V1 P S V X X1 Y Y1 KUE CC ...
Страница 123: ...OEM CAREL code 030221791 rel 2 1 21 09 07 15 4 2 Single phase wiring diagram INTERNAL TAM CP2 ...
Страница 124: ...OEM CAREL code 030221791 rel 2 1 21 09 07 16 4 3 Single phase wiring diagram INTERNAL TAM with contactor CP4 ...
Страница 125: ...OEM CAREL code 030221791 rel 2 1 21 09 07 17 4 4 Single phase wiring diagram EXTERNAL TAM with contactor CP3 ...
Страница 126: ...OEM CAREL code 030221791 rel 2 1 21 09 07 18 4 5 Three phase wiring diagram EXTERNAL TAM with contactor CP3 ...
Страница 127: ...OEM CAREL code 030221791 rel 2 1 21 09 07 19 4 6 Three phase wiring diagram INTERNAL TAM with contactor CP4 ...
Страница 141: ......