EN Series Precision Air Conditioner Owners Manual
58
Ecos
aire
®
July 2007
Data subject to change without notice.
Press
↓↓
to change the
humidity alarm set point screen.
The humidity alarms are
factory set for High=80% and Low=20%. If the room temperature goes over
“High” or under “Low” for a period greater than “Delay”, an alarm will be regis-
tered. Unit operation will not be affected. These settings can be changed as
below.
To select the alarm set point to change, press
↵
↵
repeatedly to move the cursor to
the desired position. The example is for the High humidity alarm set point.
To change the set point, press either the
↑↑
or the
↓↓
button.
To store the new value, press
↵
↵
repeatedly to move the cursor back to the top left
corner.
Startup Pre-Startup Adjustments Humidity Set Points
field press enter to move to each field, Set point, Low and High Limit
To select the humidity set point press
↵
↵
to move the cursor to the set point.
To change the humidity set point, press either the
↑↑
or the
↓↓
button to select the
desired humidity. The longer the button is held, the faster the set point
changes.
To store the new set point, press
↵
↵
. The cursor moves to the next field.
Press
Prg
, enter the password, and press
↵
↵
, as discussed in
Startup - Pre-
startup Adjustments - Controller Password
. The screen will appear as
shown.
Note: This adjustment requires the user password, see Startup - Pre-startup
Adjustments - Controller Password.
ST
ARTUP
Press
↵
to access Humidity Set Points.
To access the humidity set point
Содержание EN Series
Страница 1: ......
Страница 103: ...OEM User manual ...
Страница 104: ......
Страница 106: ......
Страница 108: ......
Страница 110: ......
Страница 115: ...OEM CAREL code 030221791 rel 2 1 21 09 07 7 KUE 4 L H A1 A2 S2 S1 V3 V1 P S V X X1 Y Y1 KUE CC ...
Страница 123: ...OEM CAREL code 030221791 rel 2 1 21 09 07 15 4 2 Single phase wiring diagram INTERNAL TAM CP2 ...
Страница 124: ...OEM CAREL code 030221791 rel 2 1 21 09 07 16 4 3 Single phase wiring diagram INTERNAL TAM with contactor CP4 ...
Страница 125: ...OEM CAREL code 030221791 rel 2 1 21 09 07 17 4 4 Single phase wiring diagram EXTERNAL TAM with contactor CP3 ...
Страница 126: ...OEM CAREL code 030221791 rel 2 1 21 09 07 18 4 5 Three phase wiring diagram EXTERNAL TAM with contactor CP3 ...
Страница 127: ...OEM CAREL code 030221791 rel 2 1 21 09 07 19 4 6 Three phase wiring diagram INTERNAL TAM with contactor CP4 ...
Страница 141: ......