OEM
CAREL code +030221791 - rel. 2.1 – 21/09/07
29
6.5
Troubleshooting
For the alarms, see instruction sheet +050003755, which is an integral part of this manual.
PROBLEM
CAUSES
SOLUTION
the humidifier does not turn on
1.
no electrical power supply;
2.
controller connectors inserted incorrectly;
3.
fuses blown;
4.
transformer fault
1.
check the protection device upstream of the humidifier
and that the power supply is present;
2.
check that the connectors are properly inserted in terminal
block;
3.
check fuses F1/F2/F3;
4.
check that the voltage at the transformer secondary is 24
Vac
the humidifier does not start
operation
1.
remote ON/OFF contact open (relay/terminals AB –
AB) on CP controller
2.
control signal not compatible with the type set
1.
close the ON/OFF contacts (relay/terminals AB – AB) on
CP controller
2.
check that the external signal is 0 to 10 V
the humidifier fills with water
without producing steam
1.
excessive backpressure in steam outlet;
2.
cylinder inlet filter blocked;
3.
lime scale in the supply tank;
4.
drain solenoid valve fault
1.
check that the steam outlet hose is not bent or choked;
2.
clean the filter;
3.
clean the supply tank;
4.
check for abnormal voltage (24 Vac) at drain solenoid
valve and/or replace the drain solenoid valve
the line thermal overload switch
is activated
1.
the thermal overload switch is undersized
2.
excess current to the electrodes
1.
check that the
thermal overload switch
is rated for a
current equal to at least
1.5 times the rated current
of the
humidifier
2.
check the operation of the drain solenoid valve, the seal of
the fill solenoid valve when not energised, drain some of
the water and re-start
the humidifier wets the duct
1.
the steam distributor is not installed correctly (too
near the top of the duct or the condensate return is
blocked);
2.
the system is oversized;
3.
humidifier on when the fan in the duct is off
1.
check that the steam distributor has been installed
correctly;
2.
decrease the steam production set on the controller;
3.
check the connection of a device (flow switch or
differential pressure switch) slaving the operation of the
humidifier to the fan in the duct (terminals AB - AB) on
the CP controller
the humidifier wets the floor
below
1.
the supply or overflow circuit has leaks;
2.
the steam outlet hose is not properly secured to the
cylinder
1.
check the entire water circuit;
2.
check that the clamp on the steam outlet is tight
Table 5.5
6.6
Alarms
For the alarms, see instruction sheet +050003755, which is an integral part of this manual.
Содержание EN Series
Страница 1: ......
Страница 103: ...OEM User manual ...
Страница 104: ......
Страница 106: ......
Страница 108: ......
Страница 110: ......
Страница 115: ...OEM CAREL code 030221791 rel 2 1 21 09 07 7 KUE 4 L H A1 A2 S2 S1 V3 V1 P S V X X1 Y Y1 KUE CC ...
Страница 123: ...OEM CAREL code 030221791 rel 2 1 21 09 07 15 4 2 Single phase wiring diagram INTERNAL TAM CP2 ...
Страница 124: ...OEM CAREL code 030221791 rel 2 1 21 09 07 16 4 3 Single phase wiring diagram INTERNAL TAM with contactor CP4 ...
Страница 125: ...OEM CAREL code 030221791 rel 2 1 21 09 07 17 4 4 Single phase wiring diagram EXTERNAL TAM with contactor CP3 ...
Страница 126: ...OEM CAREL code 030221791 rel 2 1 21 09 07 18 4 5 Three phase wiring diagram EXTERNAL TAM with contactor CP3 ...
Страница 127: ...OEM CAREL code 030221791 rel 2 1 21 09 07 19 4 6 Three phase wiring diagram INTERNAL TAM with contactor CP4 ...
Страница 141: ......