Owners Manual Ecosaire
®
EN Series Precision Air Conditioner
Refrigerant Piping Installation
Ecosaire
®
July 2009 25
Data subject to change without notice.
Air-Cooled Direct Expansion and DualCool Units Only
When shipped, remote air-cooled units contain a refrigerant holding charge.
The holding charge must be
reclaimed before removing the caps on the remote-condenser tube stubs. Failure to reclaim the
holding charge can lead to property damage and/or personal injury.
Locate the refrigerant liquid-line solenoid valves (usually two per
circuit). Some units may be equipped with manual-lift valves.
Where this is the case:
1. Using two wrenches, remove the manual-stem covers.
2. Turn the manual stems clockwise to open the valves.
stem cover
manual stem
INST
ALLA
TION
EXAMPLE
Appearance, location, and
quantity of component
s
may vary
.
EXAMPLE
Appearance, location, and
quantity of component
s
may vary
.
Manifold (by others) will also be
required for evacuation.
Reclaim
Machine
Содержание EN Series
Страница 1: ......
Страница 103: ...OEM User manual ...
Страница 104: ......
Страница 106: ......
Страница 108: ......
Страница 110: ......
Страница 115: ...OEM CAREL code 030221791 rel 2 1 21 09 07 7 KUE 4 L H A1 A2 S2 S1 V3 V1 P S V X X1 Y Y1 KUE CC ...
Страница 123: ...OEM CAREL code 030221791 rel 2 1 21 09 07 15 4 2 Single phase wiring diagram INTERNAL TAM CP2 ...
Страница 124: ...OEM CAREL code 030221791 rel 2 1 21 09 07 16 4 3 Single phase wiring diagram INTERNAL TAM with contactor CP4 ...
Страница 125: ...OEM CAREL code 030221791 rel 2 1 21 09 07 17 4 4 Single phase wiring diagram EXTERNAL TAM with contactor CP3 ...
Страница 126: ...OEM CAREL code 030221791 rel 2 1 21 09 07 18 4 5 Three phase wiring diagram EXTERNAL TAM with contactor CP3 ...
Страница 127: ...OEM CAREL code 030221791 rel 2 1 21 09 07 19 4 6 Three phase wiring diagram INTERNAL TAM with contactor CP4 ...
Страница 141: ......