ecoGEO C Installation and User Manual (Version 1.0)
page 31
Selection of system and dwelling parameters for establishing and defining the heating curve.
Table 6.2
details the recommended values for each of the parameters depending on the system chosen.
MENU 2.4.2.1. Design parameters 1
Defines the indoor and outdoor design temperature.
MENU 2.4.2.2. Design parameters 2
Defines the outdoor design temperature. For Scheme 4 it also enters the outdoor design
temperature for the 2
nd
zone.
MENU 2.4.2.3. Design parameters 3
Defines the heat emission systems in the installation (underfloor heating, fan coils or low
temperature radiators). For Scheme 4, it also adds this datum for the 2
nd
zone.
MENU 2.4.2.4. Design parameters 4
Sets the type of building insulation (good, medium or poor).
MENU 2.4.2.5. Design parameters 5
Sets the maximum outdoor temperature for heating and minimum for cooling.
MENU 2.4.3. th-Tune
Sets th-Tune indoor terminals for the heat pump.
MENU 2.4.3.1. th-Tune
If the indoor terminal type th-Tune is installed, it can be enabled here. If the installation uses
Scheme 4, the main indoor terminal and the indoor terminal for 2
nd
MENU 2.4.3.2. BMS configuration
zone addresses can be set
here. It is recommended to use values of 1 and 2, respectively.
Basic parameters for the BMS configuration of the indoor terminals. The recommended values
are shown in
Figure 4.7
.
NOTE
Remember that if your installation follows Prog 1 or Prog 2, you should not enable the indoor
environment th-Tune terminal.
Indoor environment th-Tune terminals and conventional relay type thermostats for controlling the
pump cannot coexist. This may cause the machine to malfunction.