ecoGEO C Installation and User Manual (Version 1.0)
page 61
8
Technical Specifications
8.1
Technical data table
ecoGEO C Geothermal Pumps
TECHNICAL DATA
Unit
ecoGEO C1
ecoGEO C2
ecoGEO C3
3-12
5-22
3-12
5-22
3-12
5-22
Application
Heating and DHW
-
•
•
•
•
•
•
Integrated DHW tank 170 l
-
•
•
•
•
•
•
Active cooling
-
•
•
Integrated free cooling
-
•
•
Refrigerant
Type
-
R410A
R410A
R410A
R410A
R410A
R410A
Components
Compressor
-
Scroll with Copeland inverter
Expansion valve
-
Carel Electronic
Heat exchangers
-
Alfa Laval Plates
Circulation pumps
-
Wilo high efficiency variable speed
DHW tank with coil
-
Stainless steel tank and coil
Built-in expansion vessel (12 l).
-
Heating and brine circuits
Electrical
Data
Voltage
-
230 V / 50 Hz, 1/N/PE~
Magnetothermal protection
A
32
40
32
40
32
40
Efficiency
heating output
kW
1
3-15
5-26
3-15
5-26
3-15
5-26
heating output
kW
2
3-14
5-23.5
3-14
5-23.5
3-14
5-23.5
Power consumption
kW
2
0.7-3.2
1.4-5.5
0.7-3.2
1.4-5.5
0.7-3.2
1.4-5.5
COP
-
2
4.6-5
4.6-5
4.6-5
4.6-5
4.6-5
4.6-5
EER
-
2
6.1-6.9
6.1-6.9
6.1-6.9
6.1-6.9
6.1-6.9
6.1-6.9
Active cooling output
kW
3
--
--
--
--
4-16.3
6.9-30
Free cooling output
kW
--
--
6
6
--
--
Refrigerant
Circuit
Refrigerant charge
kg
1.35
1.7
1.35
1.7
1.5
2.0
Maximum working pressure
Bar
42
42
42
42
42
42
Compressor oil
-
POE
POE
POE
POE
POE
POE
Compressor oil charge
kg
2
2.5
2
2.5
2
2.5
Heating
Circuit
Maximum/minimum temp.
ºC
60/20
Maximum working pressure
Bar
3
Flow rate
l/h
1200 - 4500
Brine
Circuit
Maximum/minimum temp.
ºC
20/-10
Maximum working pressure
Bar
3
Flow rate
l/h
1200 - 4500
Recommended antifreeze
-
4
propylene glycol / water freezing point -17 ± 2 ° C
DHW
DHW tank volume
l
170
170
170
170
170
170
Maximum working pressure
Bar
8
8
8
8
8
8
Maximum temperature
(without support)
ºC
50
50
50
50
50
50
Maximum temperature
(with support)
ºC
75
75
75
75
75
75
Soundproofing
Noise emission level
dB
42
45
42
45
42
45
Dimensions
H x W x D
mm
1800 x 600 x 700
Weight
unladen weight (without
assembly)
kg
260
270
260
270
260
270
1)
According to EN 14511, 5/2 - 30/35 º C (including circulation pumps). Provisional=pending qualification.
2)
According to EN 14511, 0/-3 - 30/35 º C (including circulation pumps). Provisional=pending qualification.
3)
According to EN 14511, 7/12 - 30/35 º C (including circulation pumps). Provisional=pending qualification.
4)
Always consult regional regulations before using antifreeze.