ecoGEO C Installation and User Manual (Version 1.0)
page 103
Application
•
DHW heating and active cooling in houses and small apartment blocks, offices or business premises
with independent heating and cooling systems. For example, facilities that combine underfloor heating
and fan coil units for cooling.
Operation
In heating mode, the heat pump pumps hot water directly to the heating system adapting to your needs. The
outlet temperature is adjusted to the type of installation and is optimized with regards to indoor and outdoor
temperatures. The flow rate is adjusted to maintain a constant working temperature difference (5°C by
default).
In cooling mode the heat pump reverses its operating cycle and cold water is driven to the cooling system
through external all/nothing zone valves. The outlet temperature is adjusted to the type of system used and is
optimized with regards to indoor and outdoor temperatures.
When there is a demand for DHW, the CHW system (Closed Hot Water Production System) is activated, which
produces DHW and heating/cooling simultaneously (maximum tank temperature 50-55°C). Once a week, the
electric heater located in the hot water tank is activated to raise the temperature to 70°C to prevent outbreaks
of legionella.
Additional control elements
Besides the heat pump control equipment you must install the following components.
•
An indoor temperature/humidity terminal (see section 5.7).
•
An outdoor temperature probe (see section 5.7).
Configuration
1.
Enter the SERVICE MENU
([Prg]
+
[Esc])
-> INSTALLER CONF. (Enter service password PW1) ->
OPERATING SCHEME -> 1 ZONE.