ecoGEO C Installation and User Manual (Version 1.0)
page 49
38
39
T1
T2
Tn
Figure 5.9.
Wiring of one or more conventional relay type thermostats.
Outdoor temperature probe
The outdoor temperature probe is connected by twin-pole cables to the lower terminal strip of the electrical
cabinet, as indicated in
Figure 5.11
(See also sections 8.3 to 8.6). To install the temperature probe, bear in mind
the following recommendations.
1.
Install the outdoor temperature probe to the north or northeast of the house.
2.
Place the outdoor temperature probe in a place that is well ventilated but sheltered from the wind.
3.
Do not install the outdoor temperature probe within a distance of 1 m from windows or doors to avoid
the possible effect of warm air currents.
4.
Use cable of 50 m maximum length and a minimum diameter of 0.75 mm
2
for connecting the
temperature probe. For longer lengths (up to 120 m) 1.5 mm
2
cable is recommended.
North
Recomended
Not recomended
Figure 5.10.
Recommended locations for installation of the outdoor temperature probe.