Firmware V7.16.x
16.05.2023
79/183
7.1.4 Terminal assignment of the CAN bus terminals
The terminals for the connection to the first CAN bus segment CAN1 (standard) and second CAN bus segment
CAN2 are located on the device at the bottom. See chapter
CAN bus - Connection of E*LDS Components
for
further details about the range of functions of the two interfaces.
Connection to the CAN bus, shown here using the first CAN bus segment (CAN1) as example. This also
applies for the second CAN bus segment (CAN2).
CAN1 - First CAN bus segment
Standard
CAN2 - Second CAN bus segment
VSC 5110 / VSC 5510 only: Repeater function
Terminal No.
Function
Wire colour
Terminal No.
Function
Wire colour
4
3
2
1
CAN-HIGH
CAN-LOW
CAN-GND
SHLD (Shield)
white
brown
green
shield
24
23
22
21
CAN-HIGH
CAN-LOW
CAN-GND
SHLD (Shield)
white
brown
green
shield
CAN bus - Connection of E*LDS Components
safety and connection instructions
DANGER
Warning about dangerous electrical voltage!
If mains voltage is connected to the CAN bus
terminals, this will result in the destruction of all components connected to the CAN bus!
CAN bus supply lines must be shielded (cable type:
LiYCY 2x2x0.75 mm
2
)! As a general rule, care
should be taken to ensure that signal cables and cables carrying mains voltage are routed in separate
cable channels.
Wiring Variant A
: Device is a node in a CAN bus segment with other devices before and after this,
no
terminating resistor
required.
Wiring Variant B
: Device is at the start / end of a CAN bus segment,
terminating resistor required
.
Recommendation: Use of the terminal set for CAN bus termination; see chapter
Содержание Virtus 5 Series
Страница 14: ...Firmware V7 16 x 16 05 2023 14 183 https edp eckelmann de edp lds _S88KwDvR7a ...
Страница 71: ...Firmware V7 16 x 16 05 2023 71 183 ...
Страница 91: ...Firmware V7 16 x 16 05 2023 91 183 ...
Страница 98: ...Firmware V7 16 x 16 05 2023 98 183 3 Special keyboard for convenient input of time ranges e g for week timers ...
Страница 130: ...Firmware V7 16 x 16 05 2023 130 183 Note GLT Building Control and DDC Digital Direct Control ...