Firmware V7.16.x
16.05.2023
152/183
3 Menu 4-3 - Pack controllers
The submenu for configuration of the pack controllers is called using this button. All important
parameters and the status of the pack controllers are displayed there. Pack controllers can be added using the
"New entry" button. Already added pack controllers can be selected and configured using the corresponding
screen.
The assigned CAN bus address, diverse statuses and operating statuses are also displayed.
Symbol
Meaning
The status of the connection (communication) with the node is OK
The status of the connection (communication) with the node is unknown
The node has failed
The node has been unloaded
The status of the node is OK
The node has alarm status
The screen contains the following parameters:
Configuration Pack Controller
Entry
Default
Name
Name of the node, e.g. Deep freeze pack max. 19 characters
-
Position
Position designation of the node, e.g.
VSTK_01
5 characters
-
Priority
Alarm and message priority 0..99
0..99
-
Address
CAN bus address 101..109
These fields cannot be edited!
-
Serial number
Serial number of the controller
-
Firmware version
Firmware version of the controller
-
Integrated using
The controller is connected to the system
centre via this interface
-
Pack number
Pack number
1 = CAN bus address 101 …
9 = CAN bus address 109
-
Remote control using terminal mode
The terminal mode screen is opened using the
Remote Control
button. All parameters of the pack controller can
be configured in the terminal mode. For more information, see chapter
Remote control of E*LDS components
Any pack controller can be removed from the system again using the "Delete" button. A pack controller
can only be deleted if it has previously been switched off and accordingly signalled as failed!
Содержание Virtus 5 Series
Страница 14: ...Firmware V7 16 x 16 05 2023 14 183 https edp eckelmann de edp lds _S88KwDvR7a ...
Страница 71: ...Firmware V7 16 x 16 05 2023 71 183 ...
Страница 91: ...Firmware V7 16 x 16 05 2023 91 183 ...
Страница 98: ...Firmware V7 16 x 16 05 2023 98 183 3 Special keyboard for convenient input of time ranges e g for week timers ...
Страница 130: ...Firmware V7 16 x 16 05 2023 130 183 Note GLT Building Control and DDC Digital Direct Control ...