Firmware V7.16.x
16.05.2023
175/183
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
124
Coldroom door Mxx*
Coldroom door of component Mxx
*
open
Close coldroom door, check door
contact and cable connections
126
Defrost thermostat Mxx*
or
temporal defrost. Mxx*
Defrost thermostat fault at component Mxx*
or
Defrost end time at component Mxx*
Check component Mxx
*
128
Sensor fault x* Mxx*
* designates the sensor
number
(1 to 4)
Sensor fault on component Mxx
*
. Possible
causes:
Sensor has been removed
Sensor short-circuit
Electrical interference has occurred
Check connection cable
Check shield
Replace affected sensor
Sensor fault Mxx*
Sensor fault on component Mxx
*
. Possible
causes:
Sensor has been removed
Sensor short-circuit
Electrical interference has occurred
Check connection cable
Check shield
Replace affected sensor
132 133
High temp. Mxx*
Low temp. Mxx*
High / low temperature at component Mxx
*
Parametrisation
Temperature sensor
Check system
150
Verdichterstör. Mxx*
Compressor fault of an AHT case Mxx
*
with
Danfoss controller
Check compressor for component Mxx
*
*
160
Pressostat Mxx*
Pressure fault at component Mxx
*
Condenser Mxx *
*
dirty, check
164
LP too low Mxx*
Lower limit value t
0
at compressor Mxx
*
undercut
Check compressor Mxx
*
179
External alarm Mxx*
Error message of component Mxx
*
Check component Mxx
*
Wurm node error messages
128
Sensor fault Wxx*
Sensor fault on component Wxx
*
. Possible
causes:
Sensor has been removed
Sensor short-circuit
Electrical interference has occurred
Check connection cable
Check shield
Replace affected sensor
132
High temp. Wxx*
High / low temperature at component Wxx
*
Parametrisation
Temperature sensor
Check system
Other
180
Service Mode
The automatic transmission of alarms has
been deactivated temporarily for maintenance
purposes.
Reset Service Mode, see
*
xxx
stands for the CAN bus addresses 1..127
Mxx
stands for the Modbus addresses M1..M50
Wxx
stands for the address of a node from the Wurm company
Содержание Virtus 5 Series
Страница 14: ...Firmware V7 16 x 16 05 2023 14 183 https edp eckelmann de edp lds _S88KwDvR7a ...
Страница 71: ...Firmware V7 16 x 16 05 2023 71 183 ...
Страница 91: ...Firmware V7 16 x 16 05 2023 91 183 ...
Страница 98: ...Firmware V7 16 x 16 05 2023 98 183 3 Special keyboard for convenient input of time ranges e g for week timers ...
Страница 130: ...Firmware V7 16 x 16 05 2023 130 183 Note GLT Building Control and DDC Digital Direct Control ...