6.13 Firmware Update
The system centre is supplied with the current firmware, ready for operation. Future software versions can be
loaded into the system centre as required by means of a firmware update, and thus updated.
ATTENTION
Damage to the installation and stock loss! Before
the firmware update, the affected system
component or the system must be brought into a safe state as the shutdown of the controller during the
firmware update can have undesired effects on the system component and/or the system.
Caution: data loss!
The loading of software via firmware update must not be interrupted at any time.
The mains plug and the USB stick must
not
be disconnected during the firmware update. It must be
ensured that power is supplied throughout the entire procedure. Any interruption of the firmware
update can result in an inoperative controller. In some cases, a change of the firmware version can
result in the loss of all the specified setpoints in the system centre. As a precaution, the settings should
therefore be backed up by saving them using the LDSWin PC software before the replacement. After
the firmware update, the saved settings can be reloaded into the system centre from LDSWin.
A firmware update must only be performed by trained personnel or at the factory by the manufacturer.
Further details about the current firmware can be found in
Содержание Virtus 5 Series
Страница 14: ...Firmware V7 16 x 16 05 2023 14 183 https edp eckelmann de edp lds _S88KwDvR7a ...
Страница 71: ...Firmware V7 16 x 16 05 2023 71 183 ...
Страница 91: ...Firmware V7 16 x 16 05 2023 91 183 ...
Страница 98: ...Firmware V7 16 x 16 05 2023 98 183 3 Special keyboard for convenient input of time ranges e g for week timers ...
Страница 130: ...Firmware V7 16 x 16 05 2023 130 183 Note GLT Building Control and DDC Digital Direct Control ...