Firmware V7.16.x
16.05.2023
118/183
7 Menu 2-7 - Signal inputs
This button is used to call up the signal and alarm inputs of the system centre. All important
parameters and the status of the digital inputs are displayed there.
The screen contains the following parameters:
Signal inputs
Message text
Message text of the signal input (digital input)
Priority XX
Priority of the signal / alarm input
Delay time [Min.] XX
Delay time of the signal / alarm in minutes
Quiescent current (low-active) X
Alarm is signalled if
- quiescent current = Yes: (signal voltage not present, low-active)
- quiescent current = No: (signal voltage is present, high-active)
Input X
Connection of the input
1)
Status XX
Current status of the input:
OK = light grey: no signalling
Wait = yellow: signalling, delay time running,
message = green: no alarm
alarm = red: signalling, alarm / message has been tripped
1)
Designations of the supported modules / inputs:
CI 4x00 system centre, internal inputs IN1 / IN2 (terminals A1, A2 / B1, B2)
SIOX1 1st extension module, inputs 1 .. 12
SIOX2 2nd extension module, inputs 1 .. 12
SIOX3 3rd extension module, inputs 1 .. 12
SIOX4 4th extension module, inputs 1 .. 12
DDC1 1st GLT DDC module 1
DDC2 2nd GLT DDC module 2
DDC3 3rd GLT DDC module 3
DDC4 4th GLT DDC module 4
Note: GLT = Building Control System and DDC = Digital Direct Control
The digital signal and alarm inputs are configured using Menu 4-1-2. Further information about the
functions is contained in the chapter
.
Содержание Virtus 5 Series
Страница 14: ...Firmware V7 16 x 16 05 2023 14 183 https edp eckelmann de edp lds _S88KwDvR7a ...
Страница 71: ...Firmware V7 16 x 16 05 2023 71 183 ...
Страница 91: ...Firmware V7 16 x 16 05 2023 91 183 ...
Страница 98: ...Firmware V7 16 x 16 05 2023 98 183 3 Special keyboard for convenient input of time ranges e g for week timers ...
Страница 130: ...Firmware V7 16 x 16 05 2023 130 183 Note GLT Building Control and DDC Digital Direct Control ...