Firmware V7.16.x
16.05.2023
132/183
Interface COM1/Modem
The COM1 interface is configured in this screen. The COM1 interface can be used as modem or as
COM port server. When the interface is used as COM port server, the serial interface of the GLT 3010 can be
accessed via the Ethernet connection of the Virtus 5.
Use of the interface as modem
Interface - COM1/Modem
Input
Default
Telephone number
Telephone number of the modem at the system
centre (connected to COM1)
max. 19 characters
-
Dialling prefix
Number for the outside line
max. 8 digits
-
MSN
19-digit terminal device identification number
- for direct outside line, this is the telephone
number (without the dialling prefix))
- in the normal case (i.e. for extensions), this is
the direct dial number
max. 19 characters
0
PIN
PIN
-
Alarm if modem not available
Should an alarm be signalled if the modem is
not detected?
If the check mark is set and no modem is
detected at the interface,
the alarm "Modem Fault" is output after 2
minutes.
Y/N
Y
Use of the interface as COM port server
Interface - COM1 / COM port
server
Input
Default
TCP port
Input of the TCP/IP port of the COM
port server
Numbers (1..65535)
1041
Baud rate
Baud rate of the serial connection to the
GLT 3010
300, 1200, 2400, 4800, 9600, 19200,
38400, 57600, 115200
38400
For detailed information, see chapter
For detailed information, see chapter
.
Содержание Virtus 5 Series
Страница 14: ...Firmware V7 16 x 16 05 2023 14 183 https edp eckelmann de edp lds _S88KwDvR7a ...
Страница 71: ...Firmware V7 16 x 16 05 2023 71 183 ...
Страница 91: ...Firmware V7 16 x 16 05 2023 91 183 ...
Страница 98: ...Firmware V7 16 x 16 05 2023 98 183 3 Special keyboard for convenient input of time ranges e g for week timers ...
Страница 130: ...Firmware V7 16 x 16 05 2023 130 183 Note GLT Building Control and DDC Digital Direct Control ...