Firmware V7.16.x
16.05.2023
128/183
The screen contains the following parameters:
Special inputs
Eingabe
Vorgabe
Message text
Shunt lock (predefined designation of the
special input)
-
Shunt lock
PriorityXX
Priority of the signal / alarm input
--, 0..99
0
Delay [sec.] XX
Delay time of the signal / alarm in seconds
0..255
1
Quiescent current (low-active) X
Alarm is signalled if
- quiescent current = Yes: (signal voltage not
present, low-active)
- quiescent current = No: (signal voltage is
present, high-active)
Y/N
N
Signal input
Module
Module
1)
to which the message / alarm signal
is connected
SIOX1 ..SIOX4
-
Submodule XX
Submodule
1)
to which the message / alarm
signal is applied; this is ONLY visible if
module=DDC1..DDC4 has been selected
1..4
-
Input XX
Input
1)
to which the message / alarm signal is
applied
1..12
-
Status XX
Current status of the input:
OK = light grey, no signalling
Waiting = yellow: signalling, delay time running,
Message = green: no alarm
Alarm = red: signalling, alarm / message has
been tripped
-
-
1)
Designations of the supported modules / inputs:
CI 4x00
system centre, internal inputs IN1 / IN2 (terminals A1, A2 / B1, B2)
SIOX1 1. extension module, inputs 1 .. 12
SIOX2 2. extension module, inputs 1 .. 12
SIOX3 3. extension module, inputs 1 .. 12
SIOX4 4. extension module, inputs 1 .. 12
DDC1 1. GLT DDC module 1
DDC2 2. GLT DDC module 2
DDC3 3. GLT DDC module 3
DDC4 4. GLT DDC module 4
Note: GLT = building control and. DDC = Digital Direct Control
Only those SIOX modules and GLT PLC modules are provided for selection that have been configured
accordingly in screen 4-1-1! A description of the functions can be found in chapter
Содержание Virtus 5 Series
Страница 14: ...Firmware V7 16 x 16 05 2023 14 183 https edp eckelmann de edp lds _S88KwDvR7a ...
Страница 71: ...Firmware V7 16 x 16 05 2023 71 183 ...
Страница 91: ...Firmware V7 16 x 16 05 2023 91 183 ...
Страница 98: ...Firmware V7 16 x 16 05 2023 98 183 3 Special keyboard for convenient input of time ranges e g for week timers ...
Страница 130: ...Firmware V7 16 x 16 05 2023 130 183 Note GLT Building Control and DDC Digital Direct Control ...