Firmware V7.16.x
16.05.2023
59/183
6.2.1 SIOX - connection to the system centre
The individual SIOX extension modules are supplied with power from the controller via SIOX-SUPPLY
(terminals 91/92/93/94/95) and connected to each other in series via SIOX data cables (SIOX OUT and SIOX
IN using RJ45).
ATTENTION
Danger of destruction of components!
SIOX extension modules may
only
be connected
to each
other or the controller when no voltage is present! In the event of an Ethernet network cable with PoE
(Power over Ethernet) being used instead of the SIOX data cable (RJ45) damage can occur to
participating network devices!
SIOX operating instructions
Comprehensive details on the SIOX extension modules and their current operating instructions can be
found here:
https://edp.eckelmann.de/edp/lds/_S88KwDvR7a