5.8.5 Automatic transmission of alarms via Pushover
The controller provides the possibility to automatically forward alarms and messages in plain text from the
E*LDS system via the "Pushover" message service (Menu 4-1-7). A user account must be created at
"Pushover" (
) to use this service. The following information is transmitted in the Pushover
message :
Name of the E*LDS component
Position number (CAN bus address)
Message text
Priority
Date and time of the receive or send time stamp
5.8.6 Automatic transmission of alarms via E-Mail
The controller provides the possibility to automatically forward alarms and messages in plain text from the
E*LDS system via E-Mail (Menu 4-1-7). The following information is transmitted in the E-Mail message:
Name of the E*LDS component
Position number (CAN bus address)
Message text
Priority
Date and time of the receive or send time stamp
ATTENTION
Risk of the failure of alarm messages for Pushover and thus no alarm signalling in the event of
problems!
It
cannot be ensured
that the Pushover message is delivered securely and promptly;
therefore transmission of Pushover messages should not be configured as the only alarm path!
ATTENTION
Risk of the failure of alarm messages for E-Mail and thus no alarm signalling in the event of
problems!
It
cannot be ensured
that the E-Mail is delivered securely and promptly to the recipient,
therefore transmission of E-Mail messages should not be configured as the only alarm path!
Содержание Virtus 5 Series
Страница 14: ...Firmware V7 16 x 16 05 2023 14 183 https edp eckelmann de edp lds _S88KwDvR7a ...
Страница 71: ...Firmware V7 16 x 16 05 2023 71 183 ...
Страница 91: ...Firmware V7 16 x 16 05 2023 91 183 ...
Страница 98: ...Firmware V7 16 x 16 05 2023 98 183 3 Special keyboard for convenient input of time ranges e g for week timers ...
Страница 130: ...Firmware V7 16 x 16 05 2023 130 183 Note GLT Building Control and DDC Digital Direct Control ...