1 Menu 1 - Alarms and messages
Tapping this button opens the alarm list screen; this does not show any entries then. The "Current
Alarms" view is displayed as default. Use the left "Message List" "tab" button to change to the message list. The
message list contains all messages and current alarms with the priority 0..99 that have been listed by the
system centre from connected E*LDS components system-wide and the activated external alarms signalled via
the digital inputs.
If any E*LDS component signals an alarm, the button in the main menu changes to red. Tapping this
button opens the alarm list screen in which the current alarms or alarms that can be acknowledged are now
listed.
The current alarms (only priority 1..99) are shown in the alarm list until they are signalled as rectified and have
been acknowledged by the operator.
This symbol must be confirmed for the acknowledgement of the rectified alarms. Acknowledged
alarms are automatically moved into the message list, forming the history of the alarms that have occurred in
the installation.
The screen contains the following information
Incoming:
Date and time of alarms and messages as they occurred (receive time stamp).
Outgoing - in the alarm list:
If any red alarm symbol can be seen in this column, this means that alarms with
the priority 1..9 are still pending, the faults have not yet been rectified and these alarms cannot be
acknowledged! On the other hand, if there is a date and time in this column, the problems or causes of the
alarm have been rectified and the alarm has gone and can be acknowledged using the acknowledge button in
the right area. These alarms are then removed from the alarm list; however they are always still in the message
list.
Содержание Virtus 5 Series
Страница 14: ...Firmware V7 16 x 16 05 2023 14 183 https edp eckelmann de edp lds _S88KwDvR7a ...
Страница 71: ...Firmware V7 16 x 16 05 2023 71 183 ...
Страница 91: ...Firmware V7 16 x 16 05 2023 91 183 ...
Страница 98: ...Firmware V7 16 x 16 05 2023 98 183 3 Special keyboard for convenient input of time ranges e g for week timers ...
Страница 130: ...Firmware V7 16 x 16 05 2023 130 183 Note GLT Building Control and DDC Digital Direct Control ...