5.8.4.2 Extended alarm destinations 4..15
The extended alarm destinations provide significantly more options for differentiated remote alarm signalling as
compared with EASY alarm destinations.
The alarm destinations are freely configurable in LDSWin and can be assigned to any destinations. Further
information about the functions is contained in the chapter
.
The following settings are possible for these alarm destinations (these are only displayed in the system centre):
Name of the alarm destination (freely definable)
Destination type / service: LDSWin, SMS via D1, Anny Way or FAX
Telephone number with entry whether outside line or internal call - function as primary or alternative
destination
If alternative destination,
name of the primary destination
Individual priorities or priority groups can be assigned using the LDSWin PC software: Individual value or range
with start and end values or ALL (without priority X9).
In this way, alarms and messages can be specifically signalled to the responsible fault service for the
maintenance group. In this way, alarm signals are sent selectively, resulting in reduction of service and
maintenance costs and efficient service assignments.
Example: Procedure for configuration using the LDSWin PC software
Specify alarm destinations
The refrigeration pack system should notify the service centre and the building control system should notify
the caretaker.
Specify the priorities and priority groups and assign them to the alarm destinations
Refrigeration pack system: Priorities 0..9Entire installation / building control systems: Priorities 10..99
Set the priorities in the components accordingly
The meaning of the priorities X1 and X2 in combination with the alarm relay must be observed, see chapter
: components / controller of the refrigeration pack system signal with the priorities 0..9
components of the building automation (heating, air conditioning,..) with the priorities 10..99
The extended alarm destinations 4..15 are only displayed (read-only) in the system centre and can
only be edited using the LDSWin PC software.
The settings must be planned and entered carefully. In the event of incorrect configuration, there is
potential for alarms to be sent to the wrong alarm destinations and not given the required attention
there.
Содержание Virtus 5 Series
Страница 14: ...Firmware V7 16 x 16 05 2023 14 183 https edp eckelmann de edp lds _S88KwDvR7a ...
Страница 71: ...Firmware V7 16 x 16 05 2023 71 183 ...
Страница 91: ...Firmware V7 16 x 16 05 2023 91 183 ...
Страница 98: ...Firmware V7 16 x 16 05 2023 98 183 3 Special keyboard for convenient input of time ranges e g for week timers ...
Страница 130: ...Firmware V7 16 x 16 05 2023 130 183 Note GLT Building Control and DDC Digital Direct Control ...