Firmware V7.16.x
16.05.2023
102/183
After the login, another symbol is shown automatically on the left next to the padlock; this symbol is used in the
service mode for suppression of the remote alarm signalling.
Symbol
s
Description
The remote alarm signalling is active if the symbol is white.
If the symbol is yellow, the remote alarm signalling has been deactivated for a duration selected by the user; see chapter
Service Mode - Suppression of the remote alarm signalling
.
9.1.2.1 Service mode - suppression of remote alarm signalling
After the login, another symbol is shown automatically on the left next to the padlock; this symbol is used in the
service mode for suppression of the remote alarm signalling.
Symbol
s
Description
This button is not displayed until
after
successful login to the device. The remote alarm signalling is active if the symbol is white.
The symbol must be tapped to activate the suppression of the remote alarm signalling.
If the symbol is yellow, the remote alarm signalling has been deactivated for a duration selected by the user and remains visible
in the display until the delay time has elapsed.
The screen contains the following parameters
Login
Input
Default
Delay [min.]
Input of the delay time for suppression of the remote
alarm signalling. The symbol is yellow if service mode
has been activated.
Service mode is deactivated again by input of 0 minutes,
the symbol becomes white again and all alarms are then
forwarded again immediately via modem, network, relays
or horn!
0, 1..255
60
The service mode can also still be active (yellow symbol) if the system centre is locked down. See
chapter
for further details about the suppression of the remote alarm signalling.
Содержание Virtus 5 Series
Страница 14: ...Firmware V7 16 x 16 05 2023 14 183 https edp eckelmann de edp lds _S88KwDvR7a ...
Страница 71: ...Firmware V7 16 x 16 05 2023 71 183 ...
Страница 91: ...Firmware V7 16 x 16 05 2023 91 183 ...
Страница 98: ...Firmware V7 16 x 16 05 2023 98 183 3 Special keyboard for convenient input of time ranges e g for week timers ...
Страница 130: ...Firmware V7 16 x 16 05 2023 130 183 Note GLT Building Control and DDC Digital Direct Control ...