10
Instruction Manual IM02602008E - Rev. D
Transformer Temperature Controllers
IM02602008E - Rev. D May 2019 www.eaton.com
2.4.2.9 Fan Power
WARNING
POWER TO THE FAN(S) MUST BE FUSED AT THE SOURCE
AT A LEVEL APPROPRIATE FOR THE SELECTED WIRING.
1. Connect input power (line or +) for the fan(s) to termi-
nal #1, shown in Figure 9, TC - Typical External Wiring
Diagram.
2. Connect input power (line2, neutral, or -) for the fan(s) to
terminal #2.
3. Connect the passed-through output power (line2, neutral
or -) to the fan(s) to terminal #3.
4. Connect the fused, switched output power to the fan(s)
to terminal #4.
otee:
N
The fuses built into the TC-100 are standard 1/4” x
1-1/4”, 250 Vac, 20 Amps maximum rating. Lower rat-
ings may be used, as required, based upon the appli-
cation’s power supply, wire size, and fan(s).
2
3
4
5
6
7
8
9
10
11
12
13
Transformer
Temperature
Controller
1
2
3
4
1
J2
1
2
3
4
J8
J1
J7
J9
J10
(+) 2
(-) 1
1
2
3
4
1
2
3
4
5
6
7
8
FAN
POWER
FAN 1
FAN 2
BURDEN
<1K OHM
R
4-20mA
LOOP
Modbus
NETWORK
T
REMOTE TRIP
REMOTE ALARM
NON CURRENT
CARRYING GROUND
120/240VAC
CONTROL
POWER
TRIP/
ALARM
POWER
L
C
R
+
-
+
-
+
-
+
-
THERMOCOUPLES
in TRANSFORMER
WINDINGS
THERMOCOUPLE
in CABINET
AMBIENT AIR
4-20mA
OUTPUT
A
B
COMMON
Shield
THERMOCOUPLE INPUTS
RS-
485 Mo
dbus
MONITOR
(TC-50 Modus and
TC-100 Only)
Figure 9, TC - Typical External Wiring Diagram