7. Troubleshooting
The TC models are very reliable if installed and operated
properly.
If, for some reason, your TC does not function properly,
first confirm that it is installed properly. See Section 2,
Installation.
If the TC malfunctions after it has been operating routinely,
refer to Table 4, Troubleshooting Chart.
This Troubleshooting Chart identifies causes and solutions
to the malfunction. For further assistance contact the
Customer Integrity Team at [email protected] or call-
ing 1-844-435-8982.
Table 4 - Troubleshooting
Condition
Probable Cause
Solution
Electrical
Display shows A.TMP-ND
No winding temperature decrease within five (5)
minutes of Fan(s) turn on
Verify proper fan operation.
Display shows A.T-R-CON
Thermocouple wired reverse polarity
Verify proper polarity of thermocouple connections.
Display shows A.T-O-CKT
Thermocouple Open Circuit
Winding temperature (s) colder than internal con-
troller temperature
Verify thermocouple is connected properly.
Replace thermocouple if broken.
If this is a typical operating condition, disable
reverse thermocouple detection
Display shows A.OVRTMP
Winding temperature(s) exceed Alarm threshold
Verify proper alarm setpoint and if correct trouble-
shoot and repair any transformer overloading, fan
failure, airflow blockage, etc.
Display shows A.AIR-ND (TC-100 only)
Discrete Input Activation
Troubleshoot reason for discrete input activation
and make any necessary repairs
Display shows A.FANWEAR (TCC-100 only)
Total fan operating time has exceeded the pro-
grammed threshold
Perform any required fan maintenance based on
this operating time and Reset the FANWEAR hours
via the front panel Reset menu
Display shows A.FAN ONT (TC-100 only)
Fan has been operating continuously for at least
24 hours
Troubleshoot and repair any potential transformer
overloading, fan failure, airflow blockage, etc.
Note: This may be a normal operating condition
during periods of high ambient temperature and
heavy transformer loading
Display shows A.FRAM or A.EEPROM or A.ISO-OR
Internal Controller Failure
Return controller for repair.
Fan(s) not turning on
Improper programming
Open Fuse
Bad wiring/fan
Verify proper programming of fan mode and set-
points
Determine/repair cause of fuse opening. Replace
fuse
Rewire/replace fan, as required