22
Instruction Manual IM02602008E - Rev. D
Transformer Temperature Controllers
IM02602008E - Rev. D May 2019 www.eaton.com
8. Scroll to
ON
or
OFF
using the
and
arrows.
9. Press
Select
to enter your choice. INPUT 1 displays.
10. Press
Back
once or twice to return to the sub-
menus, or three times to exit the program
.
4.1.2.2.6.4 Input 2 (INPUT-CH/CH-ON or OFF/INPUT2)
Sets thermocouple On/Off control for input to
ON
or
OFF
.
The default is
ON
.
1. Press
Prog
and enter your password. A sub-menu
displays.
2. Scroll to I
NPUT-CH
using the
and
arrows.
3. Press
Select
. A sub-menu displays.
4. Scroll to
CH-ON.OFF
using the
and
arrows.
5. Press
Select
. A sub-menu displays.
6. Scroll to
INPUT 2
using the
and
arrows.
7. Press
Select
. A sub-menu displays.
8. Scroll to
ON
or
OFF
using the
and
arrows.
9. Press
Select
to enter your choice.
INPUT 2
displays.
10. Press
Back
once or twice to return to the sub-
menus, or three times to exit the program.
4.1.2.2.6.5 Input 3 (INPUT-CH/CH-ON or OFF/INPUT3)
Sets thermocouple On/Off control for input to
ON
or
OFF
.
The default is
ON
.
1. Press
Prog
and enter your password. A sub-menu
displays.
2. Scroll to
INPUT-CH
using the
and
arrows.
3. Press
Select
. A sub-menu displays.
4. Scroll to
CH-ON.OFF
using the
and
arrows.
5. Press
Select
. A sub-menu displays.
6. Scroll to
INPUT 3
using the
and
arrows.
7. Press
Select
. A sub-menu displays.
8. Scroll to
ON
or
OFF
using the
and
arrows.
9. Press
Select
to enter your choice.
INPUT 3
displays.
10. Press
Back
once or twice to to return to the sub-
menus, or three times to exit the program.
4.1.2.2.6.6 Input 4 (INPUT-CH/CH-ON or OFF/INPUT4)
Sets thermocouple On/Off control for input to
ON
or
OFF
.
The default is
ON
.
Press
Prog
and enter your password. A sub-menu dis-
plays.
1. Scroll to
INPUT-CH
using the
and
arrows.
2. Press
Select
. A sub-menu displays.
3. Scroll to
CH-ON.OFF
using the
and
arrows.
4. Press
Select
. A sub-menu displays
5. Scroll to
INPUT 4
using the
and
arrows.
6. Press
Select
. A sub-menu displays.
7. Scroll to
ON
or
OFF
using the
and
arrows.
8. Press
Select
to enter your choice.
INPUT 4
displays.
9. Press
Back
once or twice to return to the sub-
menus, or three times to exit the program.
4.1.2.2.7 Input Channel Thermocouple Settings
(INPUT-CH/CH-THERM)
This is the first sub-level menu for setting the thermocouple
properties for all input channels. Pressing
Select
at this
sub-menu item provides another set of sub-menus to navi-
gate through the individual thermocouple parameters.
4.1.2.2.7.1 Thermocouple Type (INPUT-CH/CH-THERM/TYPE)
Selects the thermocouple type, between
K-Type
or
E-Type.
Default is
K-Type
.
otee:
N
All four channels must use the same thermocouple
type.
CAUTION
SELECTING THE WRONG THERMOCOUPLE TYPE WILL
RESULT IN INCORRECT TEMPERATURE READINGS, POS-
SIBLY ALLOWING THE TRANSFORMER TO OVERHEAT.
1. Press
Prog
and enter your password. A sub-menu
will display.
2. Scroll to
INPUT-CH
using the
and
arrows.
3. Press
Select
. A sub-menu displays
4. Scroll to
CH-THERM
using the
and
arrows.
5. Press
Select
. A sub-menu displays.
6. Scroll to
TYPE
using the
and
arrows.
7. Press
Select
. A sub-menu display.
8. Scroll to
K-TYPE
or
E-TYPE
using the
and
arrows.
9. Press
Select
to enter your choice.
TYPE
displays.
10. Press
Back
once or twice to return to the sub-
menus, or three times to exit the program
.
s