situated next to them. As you will see later, different functions can now be assigned to these
command buttons. In our case (internal binary input as switch) the icons stand for SWITCH ON
and SWITCH OFF. If the selected sensor is an intelligent device you can additionally select of the
status of the actuator will be sent to that device or not. (default: activated – also see
3. In the function area you can select the different functions which the switching actuator carries
out when it receives a specific command. There is a standard function for each sensor which the
MRF defines after establishing the connection to a sensor. Some functions occupy more than just
one command button, as we will see in the following function descriptions. Below there can be
various slider controls (control time, delay time, interval time etc.), which allow you to set
time-related settings for a functions.
4. In the lower area you can define the basic settings of an actuator.
In case the sensor battery is low, you can select whether or not the switching actuator should send
a warning after switching it on (output blinks once).
Regarding power recovery, you can pre-set how the switching actuator should react to it. There are
three options to choose from:
Old value (Standard): Actuator maintains the same state as before the
power failure
On: After power recovery the actuator switches the output ON
Off: After power recovery the actuator switches the output OFF
'Send Status-Message after a state change' defines if the actuator will always send out its status
message when the output state will be changed or not.
5. In the top lowest field are the command buttons:
OK: Confirms the settings entered and returns to the MRF main window.
Cancel: Discards the modifications carried out and returns to the MRF main window.
Info: Opens the Help dialog for Switching Actuator 10A
All functions of the Switching Actuator:
On / Off (Standard), occupies 2 command buttons
Switches ON resp. OFF
On / Switch-on Delay, occupies 1 command button
On Command which is executed immediately or after an adjustable Delay time
Off / On with Switch-Off delay, occupies 1 command button
Off Command which is executed immediately or after an adjustable Delay time. In case of
a delay time >0s the output will switch ON immediately and switch OFF after the delay
time.
Off / Switch-OFF delay, occupies 1 command button - New
Off Command which is executed immediately or after an adjustable Delay time. Does not
switch ON if the output is already OFF.
Off with Advance Warning, occupies 1 command button
Staircase function which switches ON immediately and switches OFF after an adjustable
time.
The Switching Actuators Output is blinking 15 seconds before it switches OFF.
Push-button/Key Mode, occupies 2 command buttons
The Switching Actuator is only ON while its sensor is activated; Otherwise it is OFF
Surge, occupies 1 command button
The Switching Actuator toggles with every sensor activation its output Value.
Blinking, occupies 1 command button - Updated
The Switching Actuator starts to blink. You can adjust the interval time and the ON/OFF
duty cycle (1-99% - minimum value cannot be <0.5s)
Activate Lock, occupies 1 command button - New
Locks the actuator against any further operation of other sensors with normal functions,
die Lock can be permanently (can only be released by a sensor with ‚Release Lock‘ function) or
after a defined Lock
time (10 minutes to 18 hours), the output action for Lock and
Release Lock can be defined (ON, OFF, old value)
Release Lock occupies 1 command button - New
Releases the Lock and allows operation of the actuator by normal functions again, the
Содержание RF System 2.42
Страница 1: ...Eaton RF System 2 42 Manual...
Страница 123: ...123 Eaton RF System 2015 Eaton Electrical Group State Syntax of RM to user...
Страница 193: ...193 Eaton RF System 2015 Eaton Electrical Group...
Страница 197: ...197 Eaton RF System 2015 Eaton Electrical Group 4 Now we select the desired function e g On switch on delay...
Страница 200: ...200 Eaton RF System Help 2015 Eaton Electrical Group 7 And assign the function Blinking to it...
Страница 218: ...218 Eaton RF System Help 2015 Eaton Electrical Group Step 4 Configuration of device type dimming actuator...
Страница 219: ...219 Eaton RF System 2015 Eaton Electrical Group Step 5 Configuration of device type analogue actuator...
Страница 220: ...220 Eaton RF System Help 2015 Eaton Electrical Group Step 6 Configuration of device type shutter actuator...
Страница 223: ...223 Eaton RF System 2015 Eaton Electrical Group Group settings analogue actuator...
Страница 224: ...224 Eaton RF System Help 2015 Eaton Electrical Group Group settings heating actuator...
Страница 225: ...225 Eaton RF System 2015 Eaton Electrical Group Group settings binary input battery supplied...
Страница 226: ...226 Eaton RF System Help 2015 Eaton Electrical Group Group settings binary input 230V Group settings Motion detector...
Страница 227: ...227 Eaton RF System 2015 Eaton Electrical Group Group settings Temperature input...
Страница 229: ...229 Eaton RF System 2015 Eaton Electrical Group Group settings Analogue input Group settings Impulse input...