If you are using both heating and cooling for a room there is a dead zone of 0.5°C between the set
points for heating and cooling of every operation mode. This means that the set point for heating
must at least be 0.5°C lower than the set point for cooling at any time.
For room 1 you can also set an offset for the measured temperature. In room 2 und 3 the offset for
the temperature is directly set in the assigned sensor.
It is possible to define a separate sum output for heating and cooling which switches on a central
heating/cooling device if one or more rooms
(with actuators or RF Radiator thermostats)
request it.
In each room a maximum of 3 window contacts (binary inputs) can be defined. If one or more
windows are opened the room will be switched to operation mode heat-/frost-protection until all
windows are closed.
If desired it is possible to define that the set-temperature or the operation mode of a room can be
changed via the local pushbuttons if the room main page is displayed. The normal function
(switching light etc.) is deactivate if a room main page is displayed and active if another main page
is displayed.
Connection to a RF Radiator thermostat:
If there is one or more RF Radiator thermostat connected to a Room the general Room regulation
is working different. It is no longer possible to connect normal actuators as heating and cooling
request to that room. The regulation of the valve position takes place in the Radiator thermostat
and not in the Room-Manager. The Room-Manager only sends Set- and Actual-temperature to the
Radiator thermostat and receives a state change from it.
The displayed state of the Room depends on the state of all connected Radiator thermostats. Only
when all thermostats are closed (0%) the Room will show “Heating OFF”. The same goes for the
Sum request of all rooms.
Using the Room menu and selecting “Valve states” the exact state of every connected Radiator
thermostat will be displayed.
If the Room-Manager is set to operation type „cooling only“ the set value for the heating request
will be 0°C.
If there is more than one Radiator thermostat connected to a Room and the Room temperature
should be measured by one of them it can be selected in the box next to “Room temperature” in
the Room configuration window in the MRF.
Содержание RF System 2.42
Страница 1: ...Eaton RF System 2 42 Manual...
Страница 123: ...123 Eaton RF System 2015 Eaton Electrical Group State Syntax of RM to user...
Страница 193: ...193 Eaton RF System 2015 Eaton Electrical Group...
Страница 197: ...197 Eaton RF System 2015 Eaton Electrical Group 4 Now we select the desired function e g On switch on delay...
Страница 200: ...200 Eaton RF System Help 2015 Eaton Electrical Group 7 And assign the function Blinking to it...
Страница 218: ...218 Eaton RF System Help 2015 Eaton Electrical Group Step 4 Configuration of device type dimming actuator...
Страница 219: ...219 Eaton RF System 2015 Eaton Electrical Group Step 5 Configuration of device type analogue actuator...
Страница 220: ...220 Eaton RF System Help 2015 Eaton Electrical Group Step 6 Configuration of device type shutter actuator...
Страница 223: ...223 Eaton RF System 2015 Eaton Electrical Group Group settings analogue actuator...
Страница 224: ...224 Eaton RF System Help 2015 Eaton Electrical Group Group settings heating actuator...
Страница 225: ...225 Eaton RF System 2015 Eaton Electrical Group Group settings binary input battery supplied...
Страница 226: ...226 Eaton RF System Help 2015 Eaton Electrical Group Group settings binary input 230V Group settings Motion detector...
Страница 227: ...227 Eaton RF System 2015 Eaton Electrical Group Group settings Temperature input...
Страница 229: ...229 Eaton RF System 2015 Eaton Electrical Group Group settings Analogue input Group settings Impulse input...