PROFIBUS Gateway EU5C-
SWD-DP
10
02/09 AWB2723-1612en
– Miniature circuit-breaker 24 V DC rated operational
current 2 A; tripping characteristics C or
– Fuse 2 A
• Miniature circuit-breaker 24 V DC for AUX
– Line protection in accordance with DIN VDE 0641
Part 11,
IEC/EN 60898:
– Miniature circuit-breaker 24 V DC rated operational
current 3 A; tripping characteristic
Z
or
– Fuse 3 A, utilisation class gL/gG
– Line protection for cable AWG 24 in accordance with
UL
508
and CSA-22.2 no. 14:
– Miniature circuit-breaker 24 V DC rated operational
current 2 A; tripping characteristics
Z
or
– Fuse 2 A
h
Please take heed of the total current consumption of your
SmartWire-Darwin network and, if necessary, plan for an
additional feeder module EU5C-SWD-PF2.
You can find information on the current consumption in
the device operating manual AWB2723-1617.
h
If any switching devices are also connected via the
SmartWire-Darwin slaves DIL SmartWire-Darwin -32-001/
002, the AUX supply will also be required. This provides
the supply for activation of the contactor coils. This supply
must be fused by an miniature circuit-breaker (3A gG/gl or
3A miniature circuit-breaker with a Z characteristic).
If switching devices with an activation power greater than
3 A are connected, an additional feeder module EU5C-
SWD-PF1 or EU5C-SWD-PF2 must be used.