Installation
50
02/09 AWB2723-1612en
Connection CANopen
For connection to the CANopen cable you require a 9-pole
SUB-D socket (e.g. PS416-ZBS-411)
X
Connect the CANopen cable by means of the CANopen
plug to the field bus interface of the gateway.
The first and last slave in a CANopen network must termi-
nate the field bus with a terminating resistor. The bus termi-
nation resistor is connected externally. In the case of
gateway EU5C-SWD-CAN the terminating resistor can be
activated by means of DIP switch 1.
Figure 21: Activation of the terminating resistor
EMC-conformant wiring of
the network
Undesired faults can occur on the field bus due to electro-
magnetic interference. This can be minimised beforehand by
the implementation of suitable EMC measures. These
include:
• EMC-conformant system configuration,
• EMC compliant cable routing,
• Measures that do not allow the occurrence of large differ-
ences in potential und
• correct installation of the CANopen network (cable,
connection of the bus connector, etc.)
OFF
ON
2 3 4 5 6 7 8
1
1
2
4
8
16
32
Node address
EU5C-SWD-CAN
Terminating resistor