Compatibility
The gateway stores the data of the devices actually
connected when the configuration button is pressed (=
stored gateway target configuration).
Each time the gateway starts it is checked whether this
configuration has been changed. If this is the case, the data
interchange between the gateway and the SmartWire
Darwin slaves is not started (missing slaves are not included
in this comparison; decisive is that the slaves found are
identical).
A project configuration is specified via the programming
system by selecting the SmartWire-Darwin slave (= planned
target configuration). This is downloaded automatically to
the gateway by the Moeller programming system during
transfer of the program to the controller.
Description
SmartWire Darwin
status LED
Data interchange
between the gateway and
SmartWire Darwin slaves
The current actual configuration complies
with the gateway target configuration.
Green continuous light
yes
A necessary SWD slave is missing or the
gateway target configuration does not
comply with the actual configuration
Flashing (red)
No
Slave addressing is active (after power
On or the download of a planned
configuration with empty modules).
Flashing (green)
No
Short circuit on the 15 V power supply or
no SmartWire Darwin slave is connected.
Red continuous light
No