PROFIBUS Gateway EU5C-
SWD-DP
8
02/09 AWB2723-1612en
The SmartWire Darwin ribbon cable is connected to the
slaves at the gateway. Connection to the PROFIBUS field bus
is effected via the standardized 9-pole PROFIBUS plug. In
addition terminals for two power supplies are available, one
for the SmartWire Darwin slaves and another 24 volts for
supply of the contactor coils in case these are also operated
via SmartWire Darwin slaves. The power supply of the
SmartWire Darwin slaves and the data communication are
conducted via the 8-pole SmartWire Darwin cable from the
gateway to the slaves.
Engineering
In connection with the SmartWire-Darwin slaves the
gateway appears as a modular slave on the PROFIBUS. Each
SmartWire-Darwin slave is a module of its own. Up to 58
SmartWire-Darwin slaves can be operated via a PROFIBUS
gateway. However, take heed of the maximum data volume
that can be exchanged via PROFIBUS. The maximum for a
PROFIBUS slave is 240 bytes of input data and 240 bytes of
output data. The SmartWire-Darwin network may be
extended up to 100 m.