Commissioning
54
02/09 AWB2723-1612en
Switching on for initial startup, a replacement or a
changed SmartWire Darwin configuration
Prerequisite for reading the configuration:
• All SmartWire Darwin slaves are connected to the
SmartWire Darwin line.
• The SmartWire-Darwin network is connected to the
gateway.
• Voltage POW is applied to the gateway and the power LED
lights up.
• The voltage AUX is applied (if necessary).
• The SmartWire-Darwin status LEDs of the SmartWire-
Darwin slaves are on or are flashing.
X
Press the configuration button on the gateway for at least
two seconds. The SmartWire status LED on the gateway
begins to flash orange. The SmartWire-Darwin status LEDs
on the SmartWire-Darwin slaves also flash. All slaves are
addressed in sequence, the complete configuration is
stored retentively (gateway target configuration). The
gateway is then restarted (see next section).
j
Warning!
If a SmartWire-Darwin slave has failed, the SmartWire-
Darwin network can still be operated with the remaining
slaves, depending on the configuration setting (even after
a repeat power up of the gateway). The failure is reported
to the application. If there is a faulty configuration and the
configuration button is pressed, only the slaves up to the
failed device are addressed and stored. Use of the
remaining slaves is not possible until the defective slave
has been replaced and the configuration has been read in
again by pressing the configuration button.