Engineering
11
02/09 AWB2723-1612en
PROFIBUS address setting
The coupling unit requires a unique PROFIBUS-DP slave
address in the PROFIBUS network. This is set on the gateway
via DIP switches (switches 2 - 8). The valid addresses are 1 -
125.
PROFIBUS connection
For connection to the field bus the standardized PROFIBUS
plug is used, e.g. ZB4-209-DS2. This also includes a
connectable bus termination resistor.
Figure 3:
Pin assignments
Baud Rates
The gateway supports operation on PROFIBUS masters at up
to 12 MB. Setting of the baud rate takes place automatically.
h
In the planning of the SmartWire Darwin network you are
also supported by the software program SmartWire-
Darwin-Assist, which automatically draws your attention
to the use of any necessary new feeder modules.
PROFIBUS-DP
Pin
Meaning
3
RxD/TxD-P
4
CNTR-P
5
DGND
6
VP (+5 V DC)
8
RxD/TxD-N
6
7
8
9
2
3
4
5
1