Engineering
43
02/09 AWB2723-1612en
Connection
Figure 16: Connection
Power supply of the gateway and supply of the SmartWire-
Darwin slave electronics are performed via the terminals
POW. The gateway contains an additional power supply unit
for the 15 V supply of the SmartWire-Darwin slaves with an
amperage of 0.7 A.
X
On the SWD gateway connect the POW and AUX supply
voltages via separate miniature circuit-breakers or fuses:
• Miniature circuit-breaker 24 V DC for POW
– Line protection in accordance with
DIN VDE 0641
Part 11, IEC/EN 60898:
– Miniature circuit-breaker 24 V DC rated operational
current 3 A; tripping characteristics
C
or
– Fuse 3 A, utilisation class gL/gG
– Line protection for cable AWG 24 in accordance with
UL
508
and CSA-22.2 no. 14:
3 A
3 A
24 V DC
0 V