Module serial number (0x2103)
Content
Subindex = 0: the subindex 0 represents the number of
SmartWire Darwin slaves registered in the target
configuration.
Subindex = 1 to the number of SWD slaves: serial number of
the slave found in the corresponding place
Read access
Data are returned from the target configuration (stored
gateway target configuration)
Write access
Not permissible.
Module parameter (0x2110)
Content
Subindex = 0: the subindex 0 returns the number of known
parameter entries in the target configuration.
Subindex = 1 - 255: parameter data
Read access
Data are returned from the target configuration (stored
gateway target configuration)
Write access
Data are written to the
Planned configuration
. The
writing may be performed only in “pre-operational” status.
The slave must support the changed parameter values.
h
At present this property is not supported by SmartWire
Darwin slaves.