![Eaton Moeller SmartWire-Darwin EU5C-SWD-CAN Скачать руководство пользователя страница 60](http://html.mh-extra.com/html/eaton/moeller-smartwire-darwin-eu5c-swd-can/moeller-smartwire-darwin-eu5c-swd-can_hardware-and-engineering_525111060.webp)
Commissioning
56
02/09 AWB2723-1612en
selected the box
Create SDO’s for Module List
in the
controller configuration). If the planned configuration
complies with the stored gateway configuration, all status
LEDs indicate a green continuous light.
Any errors that occur are indicated via the CANopen status
LED and the Config status LED.
Table 5: CAN-Status-LED
So the prerequisite for a data interchange is that the
configuration drawn up on the PLC system (= planned
configuration) complies with the configuration actually
available on the gateway. The result of this check is signalled
on the gateway via the SmartWire-Darwin configuration
LED.
Description
CAN-Status-LED
Data exchange gateway via
the CANopen to PLC
CAN interface inactive.
off
no
Baud rate detection active on the CAN
bus
Red strobe light
no
CAN baud rate detected ,waiting for a
valid target configuration
orange
no
Communication error on the CAN bus
(error warning level reached.)
Red flashing
yes
Monitoring error (node guarding/
heartbeat.)
flickering red flashing
light
only SDO
Communication error on the CAN bus
(bus Off.)
red
no
Pre-operational initialization mode -
communication only possible via SDOs
Green flashing
only SDO
Stopped - no data exchange
Green strobe light
no
Operational - data exchange is possible
via PDOs and SDOs
Green
yes
Содержание Moeller SmartWire-Darwin EU5C-SWD-CAN
Страница 8: ...4 02 09 AWB2723 1612en ...
Страница 28: ...24 02 09 AWB2723 1612en ...
Страница 56: ...52 02 09 AWB2723 1612en ...
Страница 62: ...58 02 09 AWB2723 1612en ...