Commissioning
22
02/09 AWB2723-1612en
Creating field bus communication
If a data interchange is possible between the SmartWire-
Darwin slaves and the gateway, in principle communication
between the gateway and the controller can also be performed
via PROFIBUS.
X
Connect the PROFIBUS gateway to the field bus.
X
Load the program into the controller.
The configuration of the PROFIBUS network is transferred to
the PROFIBUS master when the program is uploaded onto the
controller. The configuration of the SmartWire-Darwin network
is transferred to the PROFIBUS master when the program is
uploaded and onto the gateway. If the planned configuration
complies with the stored gateway configuration, all status
LEDs indicate a green continuous light.
Any errors that occur are indicated via the DP status LED and
the Config status LED.
Table 1:
Error messages
Description
PROFIBUS status
LED
Data interchange between
the gateway and the PLC
via PROFIBUS
Cyclic data communication runs on the
PROFIBUS. The planned configuration
complies with the gateway target
configuration.
Green continuous
light
yes
The DP master does not detect a data
interchange, because the planned
configuration does not comply with the
gateway target configuration.
Flashing (green)
yes
No communication takes place on the
PROFIBUS. No DP master is detected (for
example, on account of a wrong slave
address).
off
no
Extended DP diagnostics:
The input data from SmartWire Darwin slaves
is invalid or the necessary slaves are missing.
orange
yes