Settings
54
© 2019 DynaGen Technologies Inc
TOUGH Series Manual
Name
Parent Menu
Range
Defaults
Description
High
Point
Timers > Engine
Logic > Idle
Settings
1 to 180
0
F,
1
0
F
increments
50 F
(Warm-up Idle) Always exit idle when the temperature is above this
setting.
4.5.1.4.2 Idle Inhibit
Use this feature to prevent start up when the Idle mode switch is active.
Settings (Other Config > Idle Inhibit, in the Configuration Software these are under the switched inputs when the idle input is
enabled.)
Name
Parent Menu
Range Default
Description
Remote Start
(Start / Stop
Switched Input
Inhibit)
Other Config
> Idle Inhibit
No
Inhibit
Inhibit
No
Inhibit
Prevent the remote start switch input from starting the engine when
the idle switch is active.
Aux Start (Aux
1,2,3,4 Sensor
Autostart Inhibit)
Other Config
> Idle Inhibit
No
Inhibit
Inhibit
No
Inhibit
Prevent Auxiliary 1, 2, 3, and 4 sensors autostart feature from starting
the engine when the idle switch is active.
If the engine is in the IDLE mode because of the
feature, the remote start (start/stop) and auxiliary sensors
autostart can still start the engine.
This prevents starting when the Idle switch is active in the AUTO mode. This will also shutdown the engine if the idle switched
input is activated when the controller is in the delay-to-start, preheat, cranking, and crank reset states. The main purpose is to
prevent a remote start if the idle switch was accidentally left on.
4.5.2
Schedulers
4.5.2.1 Exerciser
The Exerciser function is used to start and run the engine periodically. The following settings configure the Exerciser function.
Exerciser Settings
(in Timers menu)
Name
Range
Default
Description
Enable
Enable ~
Disable
Disable
Enables the exerciser feature.
Delays -> Pre-
Alarm
1 ~ 20
minutes
5 min
Amount of time to display a warning before starting the engine.
Delays -> Run
Time
10 ~ 1500
minutes
30 min
Amount of time to run the engine.
Schedule -> Start
Date
1 ~ 31
8
The day of the month for the first exerciser run. This setting is only used to set
the first exerciser run. All subsequent exerciser runs use the Repeat Days
setting to determine when they should run.
If the date and time selected is already in the past for the current month then
the exerciser will be started on the next month of the given date. Also if the date
is not yet in the past but the current month does not have that date (e.g.
February 21 and a date of 31 is selected) the exerciser will run on the next
month to have that date (e.g. 31rst of March).
Schedule -> Start
Hour
0 ~ 23
12
The time of day for the exerciser run. If the "Pre-Alarm" setting above is non-
zero then this setting indicates when the pre-alarm warning countdown will
begin. The controller will start after the pre-alarm countdown is finished.
Schedule ->
Repeat Days
1 ~ 28 days
14
Number of days between each exerciser cycle. This setting is applied to all
subsequent exerciser starts after the first start.
Exerciser Sequence
Содержание Tough Series
Страница 4: ...3 2019 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Страница 11: ...Installation 10 2019 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Страница 12: ...Installation 11 2019 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Страница 13: ...Installation 12 2019 DynaGen Technologies Inc TOUGH Series Manual 2 5 Typical Wiring Diagram with RelayPak ...
Страница 17: ...Installation 16 2019 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 19: ...Installation 18 2019 DynaGen Technologies Inc TOUGH Series Manual ...