Using the Controller
21
© 2019 DynaGen Technologies Inc
TOUGH Series Manual
3.1.1
Cranking Behaviour
Crank disconnect in only monitored at the beginning of cranking. If the engine is already running the starter motor (output set to
Crank) may turn on briefly.
If the controller is programmed to use CAN J1939 or a magnetic pickup (sensor or alternator output) the controller will also
monitor AC Voltage Phase A line for frequency as a backup or secondary means of crank disconnect. This occurs even if AC
Voltage sensing is disabled in the settings.
The oil pressure is not used as a means of crank disconnect.
3.2
Using Cooldown Mode
When the controller is configured to have a cooldown period (See
section) for the engine, there is some special
functionality that must be considered.
The cooldown period is special in that during this time, it will accept a Start Command. This means if the engine is cooling
down and a start command is received, the controller will be placed back into a running mode and will not shut down.
Example:
The following is an example of how the cooldown functionality works.
1.
Remote Start contacts close
2.
Engine starts and is in the running mode
3.
Remote Start contacts open
4.
Engine starts cooldown period
5.
User presses RUN button on the front panel
6.
Engine moves back into running mode and does not shut down
7.
Engine can now only be shut down by using the OFF button or Emergency Stop input
3.3
Warnings
Warnings are conditions that alert the user to possible issues. These get enabled/disabled when you enable/disable various
settings in the controller.
Notable warnings are given in the below table.
Содержание Tough Series
Страница 4: ...3 2019 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Страница 11: ...Installation 10 2019 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Страница 12: ...Installation 11 2019 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Страница 13: ...Installation 12 2019 DynaGen Technologies Inc TOUGH Series Manual 2 5 Typical Wiring Diagram with RelayPak ...
Страница 17: ...Installation 16 2019 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 19: ...Installation 18 2019 DynaGen Technologies Inc TOUGH Series Manual ...