Settings
61
© 2019 DynaGen Technologies Inc
TOUGH Series Manual
4.6.2.1 RPM / Frequency Select
The controller has the ability to change between Primary RPM / 60Hz and Secondary RPM / 50Hz through the use of a
switched input.
The following settings must be set in order for this feature to function:
·
Switched I/O > Switched In A/B/C/D/E > Function > RPM Switch (Primary RPM / 60Hz - Secondary RPM / 50Hz
Select). The switched input is only monitored before a start signal has been received. Once a start signal has been
received changing the status of the switched input will have no effect.
·
AC Monitor > Genset Freq. > Freq. Source > Auto Selection
·
Sensors > Engine Speed > RPM Switch > Primary (Primary RPM / 60Hz)
·
Sensors > Engine Speed > RPM Switch > Secondary (Secondary RPM / 50Hz)
The table below shows the correspondence between the switched input status and the RPM / Frequency.
Switched Input
Speed / Frequency
Inactive
Primary RPM / 60Hz
Active
Secondary RPM / 50Hz
NOTE
: If enabled, the J1939 TSC1 PGN will be broadcasted according to the selected speed. Otherwise only the
warning and failure setpoints are affected by this function.
Содержание Tough Series
Страница 4: ...3 2019 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Страница 11: ...Installation 10 2019 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Страница 12: ...Installation 11 2019 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Страница 13: ...Installation 12 2019 DynaGen Technologies Inc TOUGH Series Manual 2 5 Typical Wiring Diagram with RelayPak ...
Страница 17: ...Installation 16 2019 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 19: ...Installation 18 2019 DynaGen Technologies Inc TOUGH Series Manual ...