Settings
59
© 2019 DynaGen Technologies Inc
TOUGH Series Manual
4.6.1.1 AC Voltage Select
The controller has the ability to automatically change its AC sensing (voltage and current) and display configuration through the
use of switched inputs. When using voltage select, the controller will continue to monitor the inputs for 10 seconds after crank
success. Once that time expires, the controller will then display the selected voltage configuration.
The following must be set:
1.
Two switched inputs (Switched I/O > Switched IN X > Function ) must be set to the
Volt Select 1
and
Volt Select 2
switch input functions.
2.
AC Monitor > Genset Voltage > Voltage Source must be set to
Auto Selection
. Rapid Configuration Software note: this
option will not appear unless step one if performed.
The table below shows the relation between the switched inputs status and the voltage configuration.
Volt Select 1 Input
Volt Select 2 Input
Voltage Configuration
Inactive
Inactive
3-Wire Single Phase
Active
Inactive
3-Phase (1)
Inactive
Active
3-Phase (2)
Active
Active
3-Phase (3)
NOTE
: Both
Volt Select 1
and
Volt Select 2
must be assigned to switched inputs. Otherwise the voltage sensing
will be disabled.
The below settings must be set. All except "Auto Single" are menus that contain four settings corresponding to the Volt Select
1 / Volt Select 2 inputs above.
Name
Volt Select 2 Input
Genset Voltage > Auto Nominal
These settings corresponds to the "Nominal Volts" setting under the AC Monitor > Genset
Voltage menu.
Genset Voltage > Auto Scaling
These settings corresponds to the "Scaling Factor" setting under the AC Monitor > Genset
Voltage menu.
Genset Voltage > Auto Single
Only applies when voltage sourc is set to 1-Phase 3-Wire. This determines which phases
the single phase voltage is read from: A-C or A-B.
Genset Current > Auto Rated
These settings corresponds to the "Rated Amps" setting under the AC Monitor > Genset
Current menu.
Genset Current > Auto Scaling
These settings corresponds to the "Scaling Factor" setting under the AC Monitor > Genset
Current menu.
4.6.2
Generator Frequency
Generator AC frequency display on the controller is enabled when the
is not set to Disable.
The following settings are used to configure the controller's responses to frequency measurements.
Frequency Settings
(in AC Monitor > Genset Freq.)
Name
Range
Defaul
t
Description
Freq. Source
50Hz System
(50Hz)
60Hz System
(60Hz)
Auto Selection
60Hz
Syste
m
This is the wiring configuration of the generator. Selecting Auto
Selection will use the
frequency is used.
This setting is used by the below setpoints. It does not affect the display
of AC Frequency.
Setpoints > Low Warn
(Under-Frequency
Warning)
Disable, 20 ~ 99
% in 1 %
increments
90 %
Reading at which a warning occurs.
Setpoints > Low Fail
(Under-Frequency
Failure)
Disable, 20 ~ 99
% in 1 %
increments
85 %
Reading at which a failure occurs.
Содержание Tough Series
Страница 4: ...3 2019 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Страница 11: ...Installation 10 2019 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Страница 12: ...Installation 11 2019 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Страница 13: ...Installation 12 2019 DynaGen Technologies Inc TOUGH Series Manual 2 5 Typical Wiring Diagram with RelayPak ...
Страница 17: ...Installation 16 2019 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 19: ...Installation 18 2019 DynaGen Technologies Inc TOUGH Series Manual ...