Using the Controller
26
© 2019 DynaGen Technologies Inc
TOUGH Series Manual
Low
Coolant Lvl
Failure
The "Low Coolant Level" switched input is active indicating low coolant level failure.
Over Crank Failure
The controller exhausted the crank attempts (specified in Timers > Engine Logic > Crank Attempts)
and could not start the engine.
Over
Voltage
Failure
The generator AC voltage has risen above the over voltage failure setpoint set under AC Monitor >
Genset Voltage > Setpoints.
Under
Voltage
Failure
The generator AC voltage has fallen below the under voltage failure setpoint set under AC Monitor >
Genset Voltage > Setpoints.
Regen
Needed
Failure
For electronic engines with a diesel particular filter (DPF) only. The user must perform a regeneration
before running the engine further. Continuing to ignore this message could result in the DPF being
damaged and requiring replacement.
Low Air
Pressure
Failure
The "Air Press. Fail" switched input is active. Indicates a low air pressure failure condition.
Low
Hydraulic
Failure
The "Hyd Pres. Fail" switched input is active. Indicates a low hydraulic pressure failure condition.
High
Battery
Failure
The main starter battery (the battery the controller is powered from) voltage has risen above the high
battery failure setpoint set under Sensors > Battery.
Loss Of
ECM
Comm
Failure
For electronic engines only. The "Loss of ECM" under J1939 must be enabled. The controller has not
detected engine speed, oil pressure, or engine temperature on it's CAN J1939 port.
Under
Frequency
Failure
The generator AC frequency has fallen below the under frequency failure setpoint set under AC
Monitor > Genset Freq. > Setpoints.
Over
Frequency
Failure
The generator AC frequency has risen above the over frequency failure setpoint set under AC
Monitor > Genset Freq. > Setpoints.
DPF SRVC
REQ'D!
Failure
For electronic engines with a diesel particulate filter only. Service the DFP ASAP. Damage to the
DPF is possible if the engine is run.
SERVICE
DPF!!!
Failure
For electronic engines with a diesel particulate filter only. Service the DFP ASAP. Damage to the
DPF is likely if the engine is run.
Calibration
Fail
Failure
Doosan G2 electronic engine only. Contact Doosan for more information.
High Fuel
Temp
Failure
Doosan G2 electronic engine high fuel failure. This failure comes from the engine ECM over CAN
J1939.
Hi Exhaust
Temp
Failure
Doosan G2 electronic engine high turbine exhaust temperature failure. This failure comes from the
engine ECM over CAN J1939.
FILL DEF
NOW
Failure
For electronics engines with a SCR (Seletive Catalytic Reaction) device only. The SCR needs to be
refilled. Engine may not start if this is not performed or may remain in "limp-home" mode. DEF
stands for diesel exhaust fluid.
Engine
Stall
Failure
The controller is in the RUN mode and the engine speed has fallen below the crank disconnect
speed. The engine stall must be enabled under Timers > Engine Logic.
Содержание Tough Series
Страница 4: ...3 2019 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Страница 11: ...Installation 10 2019 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Страница 12: ...Installation 11 2019 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Страница 13: ...Installation 12 2019 DynaGen Technologies Inc TOUGH Series Manual 2 5 Typical Wiring Diagram with RelayPak ...
Страница 17: ...Installation 16 2019 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 19: ...Installation 18 2019 DynaGen Technologies Inc TOUGH Series Manual ...