Using the Controller
20
© 2019 DynaGen Technologies Inc
TOUGH Series Manual
3.1
Modes, Starting and Stopping
The following table describes the different operating modes of the controller:
Modes
Mode / State
Description
OFF
When in the OFF mode, the engine cannot be remotely started.
Auto
When in the Auto mode, the engine waits to receive a start command.
Running
When engine is Running, the controller monitors engine parameters and waits to receive a
stop command.
Failure
When a failure occurs, the controller shuts down the engine and displays the reason for
failure. The unit must be reset using the front panel OFF button with the exception of Modbus.
Menu
When in the menu mode, settings can be changed and the events history may be viewed.
The following table describes the different methods for starting a controller. Unless using the Manual Run method to start the
controller, the controller must be in AUTO mode.
Starting Methods
Methods
Description
Manual Run
Pressing the Run button will start the engine. You must press the OFF button to shut down
the engine.
When this input is active the engine will start. When the input becomes inactive the engine
will shut down.
Switched inputs Momentary Start and Momentary Stop can be used for starting and stopping
of the engine. Unlike other inputs, they only have to be activated for a short period of time.
When the battery voltage drops below a certain level the engine will start and run for a
predetermined amount of time.
When the scheduled exerciser interval occurs the engine will start and run for a
predetermined amount of time.
When a scheduled event occurs the engine will start and run for the programed amount of
time.
When a properly configured Auxiliary sensor falls below / rises above a certain point the
engine will start as determined by the Auxiliary Sensors -> Mode Select settings.
J1939 Start
Start/stop command send over the J1939 CANbus. For example from the TR100 or a remote
telemetry device. The controller will display either "J1939 Run" or "J1939 Remote" as the
reason for starting.
ECM Power On
This is not a starting mode like the others. In AUTO mode if the Auto button is held for 3s the
fuel output is turned on for 1 hour. "ECM Power On" will be displayed on the screen.
Pressing and holding again within the hour will refresh for another hour. This feature can be
used to turn on or activate equipment powered by the fuel output. Often this is used by a tech
to power the ECM on an electronic engine so a diagnostic tool can obtain information from
the ECM.
WARNING
section for more information on how it affects starting and stopping.
Содержание Tough Series
Страница 4: ...3 2019 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Страница 11: ...Installation 10 2019 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Страница 12: ...Installation 11 2019 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Страница 13: ...Installation 12 2019 DynaGen Technologies Inc TOUGH Series Manual 2 5 Typical Wiring Diagram with RelayPak ...
Страница 17: ...Installation 16 2019 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 19: ...Installation 18 2019 DynaGen Technologies Inc TOUGH Series Manual ...